| Plan Review Notes For Permit 00020337 |
| Permit Number |
00020337 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | RISER DIAGRAM NOTES ON PAGE E-14 SHOW 7 | | | SETS OF 500 KCMIL WIRE FEEDING MSB AT 75 | | | DEGREES "C" WIRE DOES NOT MEET CODE, IF | | | YOU ARE USING THE 90 DEGREE COLUMN THEN | | | SHOW LISTING FOR 90 DEGREE "C" ON THE | | | TERMINATIONS PER 110-14C2 | | | | | | LOAD CALCULATION FOR MSB STILL SHOWS NO | | | LOAD FOR FIRE PUMP IT MAY NOT BE FED BY | | | MAB BUT THE CONDUCTORS THAT FEED MSB | | | ALSO FEED THE FIREPUMP!!!!!!!!!!!!!!!! |
|