2001-01-08 00:00:00*****************PROVISO****************
 REVISED DRAWINGS SHOWING THE FOLLOWING
 CORRECTIONS SHALL BE SUBMITTED PRIOR TO
 ROUGH PLUMBING INSPECTION.
  
 1.)FLOORS AND WALLS IN TOILET ROOMS AND
 RESTROOMS SHALL BE NONABSORBENT MATERIAL
 TO A HEIGHT OF 4'PER SBC SEC.1204.2.
 (PLANS NOTE PAINT BUT NOT THE TYPE.)
  
 2.)PLUMBING PLANS REFER TO DRAWING
 MUV-CIT2.SUBMIT DRAWING FOR REVIEW.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 3.)THE LAYOUT OF THE GREASY WASTE SYSTEM
 ON SHT.P1 DOESN'T CORRELATE W/SHT.P8.
  
 4.)SHT.P1-THE 6"SANITARY LINE IS DRAIN-
 ING INTO A 4" LINE.COMPLY W/SPC SEC.
 709.1
  
 5.)SHOW SQ.FOOT AREA DRAINED BY EACH
 DD,RD,& GD ON THE STORM WATER RISER.
 COMPLY W/SPC TABLES 1108.1,1108.2.
  
 6)WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC SEC.610.4.1,610.4.2.
  
 7)WATER RISER LACKS PIPE SIZES.COMPLY W/
 W/SPC TABLE 607.1.
  
 8)CLEARLY SHOW CONTINUATION POINTS OF
 SANITARY SYSTEM TO UPPER LEVELS.THE
 EXTENSIONOF THE SOIL,WASTE AND VENT
 SYSTEMTO THE UPPER FLOORS IS VAGUE.
 COMPLY W/SPC 104.2.1.
  
 9)THE SIZE OF THE GREASE TRAP SHALL BE
 APPROVED BY THE CITY OF WEST PALM BEACH
 UTILITIES.CONTACT ROD COMPO AT
 (561)835-7423.