| Date |
Text |
| 2001-01-08 00:00:00 | *****************PROVISO**************** |
| | REVISED DRAWINGS SHOWING THE FOLLOWING |
| | CORRECTIONS SHALL BE SUBMITTED PRIOR TO |
| | ROUGH PLUMBING INSPECTION. |
| | |
| | 1.)FLOORS AND WALLS IN TOILET ROOMS AND |
| | RESTROOMS SHALL BE NONABSORBENT MATERIAL |
| | TO A HEIGHT OF 4'PER SBC SEC.1204.2. |
| | (PLANS NOTE PAINT BUT NOT THE TYPE.) |
| | |
| | 2.)PLUMBING PLANS REFER TO DRAWING |
| | MUV-CIT2.SUBMIT DRAWING FOR REVIEW. |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
| | |
| | 3.)THE LAYOUT OF THE GREASY WASTE SYSTEM |
| | ON SHT.P1 DOESN'T CORRELATE W/SHT.P8. |
| | |
| | 4.)SHT.P1-THE 6"SANITARY LINE IS DRAIN- |
| | ING INTO A 4" LINE.COMPLY W/SPC SEC. |
| | 709.1 |
| | |
| | 5.)SHOW SQ.FOOT AREA DRAINED BY EACH |
| | DD,RD,& GD ON THE STORM WATER RISER. |
| | COMPLY W/SPC TABLES 1108.1,1108.2. |
| | |
| | 6)WATER SUPPLY CONTROL SHALL COMPLY W/ |
| | SPC SEC.610.4.1,610.4.2. |
| | |
| | 7)WATER RISER LACKS PIPE SIZES.COMPLY W/ |
| | W/SPC TABLE 607.1. |
| | |
| | 8)CLEARLY SHOW CONTINUATION POINTS OF |
| | SANITARY SYSTEM TO UPPER LEVELS.THE |
| | EXTENSIONOF THE SOIL,WASTE AND VENT |
| | SYSTEMTO THE UPPER FLOORS IS VAGUE. |
| | COMPLY W/SPC 104.2.1. |
| | |
| | 9)THE SIZE OF THE GREASE TRAP SHALL BE |
| | APPROVED BY THE CITY OF WEST PALM BEACH |
| | UTILITIES.CONTACT ROD COMPO AT |
| | (561)835-7423. |