| 2001-01-08 00:00:00 | PLANS SHALL BE REVIEWED AND APPROVED BY |
| | THE PALM BEACH COUNTY HEALTH DEPT.PRIOR |
| | TO REVIEW BY THIS DEPT.PER COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.101.4.7. |
| | |
| | FLOORS AND WALLS TO A HEIGHT OF 4'SHALL |
| | BE NONABSORBENT MATERIAL.SHT.ID-5.1. |
| | NOTES PAINT,BUT NOT THE TYPE.COMPLY W/ |
| | SBC 1204.2.(SEE RMS.113,113A.) |
| | |
| | PLANS SHALL BEAR THE CITY PLACE LANDLORD |
| | STAMP PRIOR TO REVIEW BY THIS DEPT. |
| | |
| | PLBG.SHEETS REFER TO CIVIL DRAWINGS FOR |
| | CONTINUATION OF WATER,SEWER,& STORM. |
| | SUBMIT THESE PLANS FOR REFERENCE.COUNTY- |
| | WIDE AMENDMENTS TO SPC 104.2.1. |
| | |
| | SHOW REQD.BACKFLOW PREVENTION DEVICE ON |
| | WATER RISER AND ON PLAN VIEW.SPC 104.2.1 |
| | |
| | SUBMIT ISOMETRIC DRAWINGS FOR SUMP |
| | DISCHARGE LINES FROM ELEVATORS AND |
| | ESCALATORS.DRAINS MAY BE REQD.TO DIS- |
| | CHARGE THRU AN INTERCEPTOR PER SPC SEC. |
| | 1004.1,1004.5. |
| | |
| | PLUMBING PLANS REFER TO DRWG.MUV-CIT2. |
| | CLARIFY AND SUBMIT THESE SHEETS IF |
| | APPLICABLE.COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.104.2.1. |
| | |
| | WATER HEATERS LOCATED ABOVE THE GROUND |
| | FLOOR SPACE SHALL HAVE A PAN WITH A |
| | DRAIN PER COUNTYWIDE AMENDMENTS SEC. |
| | 507.8.1 |
| | |
| | ALL FLOOR SINKS,FLOOR DRAINS,HAND SINKS |
| | ETC.LOCATED IN THE FOOD PREP AREA SHALL |
| | DRAIN TO THE GREASY WASTE SYSTEM.SPC SEC |
| | 1004.1,1004.4. |
| | |
| | THE FIXTURE UNIT LOAD ON THE 4"BUILDING |
| | DRAIN EXCEEDS THE TOTAL ALLOWABLE LIMIT |
| | BY TABLE 714.1 OF SPC. |
| | |
| | LAYOUT OF U/G SANITARY ON SHT.P1 DOESN'T |
| | CORRELATE W/SHT.P8.COUNTY AMENDMENTS TO |
| | SPC SEC.104.2.1,AND THERE ARE FIXTURES |
| | MISSING ON THE RISER.(SEE RMS.130,131, |
| | MOP SINK.CHECK ALL RESTROOMS.) |
| | |
| | ISOMETRICS FOR MAIN CONCESSION AREAS DO |
| | NOT CORRELATE W/ FLOOR PLAN.CLARIFY. |
| | COUNTYWIDE AMENDMENT TO SPC SEC.104.2.1. |
| | |
| | |
| | REMOVE TRAP ON OSD LINE PER SPC SEC. |
| | 1106.4.(SEE SHT.8.1) |
| | |
| | SHOW SQ.FT.AREA DRAINED BY EACH DD. |
| | COMPLY W/SPC TABLES 1108.1,1108.2. |
| | |
| | INDICATE TYPICAL DROP SIZE ON AIR RISER |
| | AND PIPE MATERIAL,SHOW VALVES. |
| | |
| | COMPRESSED AIR DRAWING ON P-5 AND P-9 DO |
| | NOT CORRELATE.CLARIFY. |
| | |
| | WATER SUPPLY CONTROL SHALL COMPLY W/SPC |
| | 610.4.1,610.4.2. |
| | |
| | WATER RISER LACKS PIPE SIZES.CLEARLY |
| | SIZE RISER DIAGRAM & COMPLY W/SPC TABLE |
| | 607.1. |
| | |
| | SHT.P9 SHOWS WATER SUPPLY EXTENDING |
| | BEYOND 4TH FLR.LEVEL.CLARIFY. |
| | |
| | SHTP9.1-WATER HEATERS INSTALLED ABOVE |
| | FIRST FLOOR SPACE SHALL BE EQUIPPED W/ |
| | PANS AND PAN DRAINS PER COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.507.8.1 |
| | |
| | WATER HEATERS SHALL BE VALVED PER SPC. |
| | SEC.501.6,506.1. |
| | |
| | HOT WATER SHALL BE INSTALLED ON LEFT |
| | SIDE PER SPC SEC.601.10. |
| | |
| | A TWO WAY CLEANOUT SHALL BE INSTALLED |
| | ENTERING AND LEAVING EACH GREASE TRAP. |
| | SPC SEC.1004.2,710.4 |
| | |
| | CLEARLY SHOW MATCH POINTS ON SANITARY |
| | RISERS TO FOUNDATION PLAN TO ENSURE |
| | DESIGN COMPLIES W/SPC.SEE PAGE P8. |
| | |
| | LABEL WATER RISERS ON P9.1 AS TO AREA. |
| | COUNTYWIDE AMENDMENTSTO SPC SEC.104.2.1. |