Plan Review Notes
Plan Review Notes For Permit 00020337
Permit Number 00020337
Review Stop P
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00PLANS SHALL BE REVIEWED AND APPROVED BY
 THE PALM BEACH COUNTY HEALTH DEPT.PRIOR
 TO REVIEW BY THIS DEPT.PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.101.4.7.
  
 FLOORS AND WALLS TO A HEIGHT OF 4'SHALL
 BE NONABSORBENT MATERIAL.SHT.ID-5.1.
 NOTES PAINT,BUT NOT THE TYPE.COMPLY W/
 SBC 1204.2.(SEE RMS.113,113A.)
  
 PLANS SHALL BEAR THE CITY PLACE LANDLORD
 STAMP PRIOR TO REVIEW BY THIS DEPT.
  
 PLBG.SHEETS REFER TO CIVIL DRAWINGS FOR
 CONTINUATION OF WATER,SEWER,& STORM.
 SUBMIT THESE PLANS FOR REFERENCE.COUNTY-
 WIDE AMENDMENTS TO SPC 104.2.1.
  
 SHOW REQD.BACKFLOW PREVENTION DEVICE ON
 WATER RISER AND ON PLAN VIEW.SPC 104.2.1
  
 SUBMIT ISOMETRIC DRAWINGS FOR SUMP
 DISCHARGE LINES FROM ELEVATORS AND
 ESCALATORS.DRAINS MAY BE REQD.TO DIS-
 CHARGE THRU AN INTERCEPTOR PER SPC SEC.
 1004.1,1004.5.
  
 PLUMBING PLANS REFER TO DRWG.MUV-CIT2.
 CLARIFY AND SUBMIT THESE SHEETS IF
 APPLICABLE.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 WATER HEATERS LOCATED ABOVE THE GROUND
 FLOOR SPACE SHALL HAVE A PAN WITH A
 DRAIN PER COUNTYWIDE AMENDMENTS SEC.
 507.8.1
  
 ALL FLOOR SINKS,FLOOR DRAINS,HAND SINKS
 ETC.LOCATED IN THE FOOD PREP AREA SHALL
 DRAIN TO THE GREASY WASTE SYSTEM.SPC SEC
 1004.1,1004.4.
  
 THE FIXTURE UNIT LOAD ON THE 4"BUILDING
 DRAIN EXCEEDS THE TOTAL ALLOWABLE LIMIT
 BY TABLE 714.1 OF SPC.
  
 LAYOUT OF U/G SANITARY ON SHT.P1 DOESN'T
 CORRELATE W/SHT.P8.COUNTY AMENDMENTS TO
 SPC SEC.104.2.1,AND THERE ARE FIXTURES
 MISSING ON THE RISER.(SEE RMS.130,131,
 MOP SINK.CHECK ALL RESTROOMS.)
  
 ISOMETRICS FOR MAIN CONCESSION AREAS DO
 NOT CORRELATE W/ FLOOR PLAN.CLARIFY.
 COUNTYWIDE AMENDMENT TO SPC SEC.104.2.1.
  
  
 REMOVE TRAP ON OSD LINE PER SPC SEC.
 1106.4.(SEE SHT.8.1)
  
 SHOW SQ.FT.AREA DRAINED BY EACH DD.
 COMPLY W/SPC TABLES 1108.1,1108.2.
  
 INDICATE TYPICAL DROP SIZE ON AIR RISER
 AND PIPE MATERIAL,SHOW VALVES.
  
 COMPRESSED AIR DRAWING ON P-5 AND P-9 DO
 NOT CORRELATE.CLARIFY.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 610.4.1,610.4.2.
  
 WATER RISER LACKS PIPE SIZES.CLEARLY
 SIZE RISER DIAGRAM & COMPLY W/SPC TABLE
 607.1.
  
 SHT.P9 SHOWS WATER SUPPLY EXTENDING
 BEYOND 4TH FLR.LEVEL.CLARIFY.
  
 SHTP9.1-WATER HEATERS INSTALLED ABOVE
 FIRST FLOOR SPACE SHALL BE EQUIPPED W/
 PANS AND PAN DRAINS PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.507.8.1
  
 WATER HEATERS SHALL BE VALVED PER SPC.
 SEC.501.6,506.1.
  
 HOT WATER SHALL BE INSTALLED ON LEFT
 SIDE PER SPC SEC.601.10.
  
 A TWO WAY CLEANOUT SHALL BE INSTALLED
 ENTERING AND LEAVING EACH GREASE TRAP.
 SPC SEC.1004.2,710.4
  
 CLEARLY SHOW MATCH POINTS ON SANITARY
 RISERS TO FOUNDATION PLAN TO ENSURE
 DESIGN COMPLIES W/SPC.SEE PAGE P8.
  
 LABEL WATER RISERS ON P9.1 AS TO AREA.
 COUNTYWIDE AMENDMENTSTO SPC SEC.104.2.1.