Plan Review Notes
Plan Review Notes For Permit 00020337
Permit Number 00020337
Review Stop E
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:001-MSB CALC DOES NOT SHOW ANY LOAD FOR TH
 FIRE PUMP!
 2-MSB LOAD CALC SHOWS LOADS FOR THE
 INDIVIDUAL PANEL, BUT THE LOAD ON THE
 PANELS DOES NOT MATCH WHAT IS SHOWN ON
 MSB CALC.215-5
 3-PLAN CALLS FOR 9 4"PIPES FOR THE SERVI
 BUT RISER SCHEDULE SHOWS 6 PLEASE FIX!
 4-RISER DIAGRAM STILL SHOWS NO DISCONNEC
 AT THE TRANSFER SWITCH FOR THE EMERG.
 FEED FROM THE GENERATOR, MAIN AT GEN.
 TO REMOTE FROM THE OTHER MAINS IN THE
 GEAR ROOM.
 5-NO PANEL SCHEDULES SHOWN FOR CCA1 THRU
 CCA4 PANELS AND ALSO CG PANEL.THERE
 ARE NO LOADS SHOWN ON THE DRAWINGS FOR
 PANEL CG?
 6-FROM DP1 AND DP2 THE PLAN SHOWS EACH
 FEEDING A SET OF PANEL THAT ARE LISTED
 AS CCA1 THRU CCA4 PLEASE CHANGE ON SET
 SO NOT CONFUSE THE INSTALLER OR INSP.
 7-ML"X" PANELS IN EACH SPACE SHOWS A #12
 WIRE ON A 60A BREAKER?ALSO SHOWS 3
 #6'S FEEDING A WIRE WAY, WHAT KIND OF
 LOAD IS THIS?
 8-THE 300KVA TRANSF. SHALL COMPLY WITH
 450-21B EXP.1&2!
 9-PAGE E1 SHOWS THE FIRE PUMP TO BE 25HP
 RISER SHOWS 100HP!GENERATOR AT 150KW
 AND RISER SHOWS 230KW?
 10-EDP LOAD CENTER SHOWS LOADS FOR THE
 INDIVIDUAL PANELS DIFFERENT THAN WHAT
 IS SHOWN AT THE PANEL CALCS. SHOW HOW
 THIS WAS DONE.SEE 215-5 FOR WHAT IS
 NEEDED!!!!!!!!
 11-EMS SYSTEM ISTHIS BEEN DELETED NEW PG
 13 SHOWS NO LOADS!!!!!!!!!!!!
 12-800AMP MAIN FOR FIRE PUMP CAN NOT BE
 MOUNTED ON THE MAIN SWITCH GEAR, IT HA
 TO BE REMOTE!!!!!!!!!!!!!!!!!!!!!!