| Date |
Text |
| 2001-01-08 00:00:00 | 1-MSB CALC DOES NOT SHOW ANY LOAD FOR TH |
| | FIRE PUMP! |
| | 2-MSB LOAD CALC SHOWS LOADS FOR THE |
| | INDIVIDUAL PANEL, BUT THE LOAD ON THE |
| | PANELS DOES NOT MATCH WHAT IS SHOWN ON |
| | MSB CALC.215-5 |
| | 3-PLAN CALLS FOR 9 4"PIPES FOR THE SERVI |
| | BUT RISER SCHEDULE SHOWS 6 PLEASE FIX! |
| | 4-RISER DIAGRAM STILL SHOWS NO DISCONNEC |
| | AT THE TRANSFER SWITCH FOR THE EMERG. |
| | FEED FROM THE GENERATOR, MAIN AT GEN. |
| | TO REMOTE FROM THE OTHER MAINS IN THE |
| | GEAR ROOM. |
| | 5-NO PANEL SCHEDULES SHOWN FOR CCA1 THRU |
| | CCA4 PANELS AND ALSO CG PANEL.THERE |
| | ARE NO LOADS SHOWN ON THE DRAWINGS FOR |
| | PANEL CG? |
| | 6-FROM DP1 AND DP2 THE PLAN SHOWS EACH |
| | FEEDING A SET OF PANEL THAT ARE LISTED |
| | AS CCA1 THRU CCA4 PLEASE CHANGE ON SET |
| | SO NOT CONFUSE THE INSTALLER OR INSP. |
| | 7-ML"X" PANELS IN EACH SPACE SHOWS A #12 |
| | WIRE ON A 60A BREAKER?ALSO SHOWS 3 |
| | #6'S FEEDING A WIRE WAY, WHAT KIND OF |
| | LOAD IS THIS? |
| | 8-THE 300KVA TRANSF. SHALL COMPLY WITH |
| | 450-21B EXP.1&2! |
| | 9-PAGE E1 SHOWS THE FIRE PUMP TO BE 25HP |
| | RISER SHOWS 100HP!GENERATOR AT 150KW |
| | AND RISER SHOWS 230KW? |
| | 10-EDP LOAD CENTER SHOWS LOADS FOR THE |
| | INDIVIDUAL PANELS DIFFERENT THAN WHAT |
| | IS SHOWN AT THE PANEL CALCS. SHOW HOW |
| | THIS WAS DONE.SEE 215-5 FOR WHAT IS |
| | NEEDED!!!!!!!! |
| | 11-EMS SYSTEM ISTHIS BEEN DELETED NEW PG |
| | 13 SHOWS NO LOADS!!!!!!!!!!!! |
| | 12-800AMP MAIN FOR FIRE PUMP CAN NOT BE |
| | MOUNTED ON THE MAIN SWITCH GEAR, IT HA |
| | TO BE REMOTE!!!!!!!!!!!!!!!!!!!!!! |