| 2001-01-08 00:00:00 | *****CONTINUATION OF PLUMBING COMMENTS** | | | | | | SHT.P-2 SHOWS FIRE LINE CONNECTED TO | | | DOMESTIC WATER LINE.LINES SHALL BE | | | SEPARATE PER SPC SEC.601.2,601.5. | | | | | | PLUMBING PLANS REFER TO SHEETS MUV-CIT2. | | | CLARIFY AND SUBMIT THESE SHEETS IF | | | APPLICABLE.COUNTYWIDE AMENDMENTS SEC. | | | 104.2.1. | | | | | | WATER HEATERS LOCATED ABOVE 1ST.FLR. | | | CEILING SHALL HAVE A PAN WITH A DRAIN | | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 507.8.1.PAN SHALL COMPLY W/SPC SEC. | | | 507.8.2. | | | | | | | | | *******************NOTE***************** | | | THE FOUNDATION PLANS WERE APPROVED BY | | | PLUMBING PLAN REVIEW ON 10/1/99 WITH A | | | PROVISO THAT CORRECT SANITARY,WATER, | | | STORM AND CONDENSATE ISOMETRICS MUST BE | | | SUBMITTED WITHIN 30 DAYS.TO DATE THESE | | | ISOMETRICS HAVE NOT BEEN SUBMITTED FOR | | | REVIEW. | | | | | | CALL (561)659-8096 IF YOU HAVE ANY | | | QUESTIONS.TIMOTHY K.LARGE,PLANS EXAMINER |
|