Plan Review Notes
Plan Review Notes For Permit 00020337
Permit Number 00020337
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00MECHANICAL REMOVED FROM THIS PLAN REVIE
 DENIED:
 1) STILL NEED SHAFT DETAIL FOR BATHROOM
 EXHAUST AND AIR CONDITIONING DUCT SYSTEM
 2) SHAFT DETAIL FOR PROJECTORS DOES NOT
 SHOW PROTECTION OF SHAFT AT BOTTOM OF
 SHAFT AT LEVEL 3 FLOOR, PROVIDE DETAIL
 OF SHAFT PROTECTION AT BOTTOM OF SHAFT
 PER 1997 SMC 601.1.2.2 AND 610.4
 3) PLEASE SPECIFY DUCT MATERIAL FOR
 PROJECTION EXHAUST DUCT
 4) SUPPY AIR DUCT FOR ATRIUM EXHAUST
 SYSTEM HAS FIRE DAMPERS. PROVIDE INFOR-
 MATION ON FIRE DAMPERS,I.E CAN THESE BE
 REMOTELY OPERATED TO OVERIDE POSITION?
 IF THESE DAMPERS SHUT THE REQUIRED
 AMOUT OF MAKE UP AIR WILL NOT BE PROVIDE
 CREATING A NEGATIVE PRESSURE ON THE
 ATRIUM. THIS ISSUE NEEDS TO BE ADDRESSED
 AND RESOLVED AS PART OF THE ATRIUM
 EXHAUST SEQUENCE OF OPERATION