Plan Review Notes
Plan Review Notes For Permit 00020337
Permit Number 00020337
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**************** PROVISO ***************
  
 1)NOTE: PLEASE SEE ORIGINAL NOTES ATTACH
 -ED. NOTE THAT A DISCONNECT IS REQ`D
 INLINE FROM GENERATOR TO TRANSFER SWITCH
 AS PER 230-70-A AND MUST BE GROUPED,230-
 72. PLEASE REVISE AND SUBMIT FOR REVIEW
 BEFORE ROUGH ELECTRICAL INSPECTION.
 NOTE THE REQ`MENTS OF 230-70-B
  
 2)NOTE; ALSO PLEASE INDICATE ALL THE
 RATINGS OF TRANSFORMERS OVER 112 1/2 KVA
 SEE 450-21-B FOR INSTALLATION REQ`MENTS.
 INDICATE THIS ON PLANS 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPEC-
 -TION. IF THERE ARE ANY QUESTIONS PLEASE
 CALL (561) 659-8096 EXT 8372/8451