| Plan Review Notes For Permit 00020337 |
| Permit Number |
00020337 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** PROVISO *************** | | | | | | 1)NOTE: PLEASE SEE ORIGINAL NOTES ATTACH | | | -ED. NOTE THAT A DISCONNECT IS REQ`D | | | INLINE FROM GENERATOR TO TRANSFER SWITCH | | | AS PER 230-70-A AND MUST BE GROUPED,230- | | | 72. PLEASE REVISE AND SUBMIT FOR REVIEW | | | BEFORE ROUGH ELECTRICAL INSPECTION. | | | NOTE THE REQ`MENTS OF 230-70-B | | | | | | 2)NOTE; ALSO PLEASE INDICATE ALL THE | | | RATINGS OF TRANSFORMERS OVER 112 1/2 KVA | | | SEE 450-21-B FOR INSTALLATION REQ`MENTS. | | | INDICATE THIS ON PLANS 215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH ELECTRICAL INSPEC- | | | -TION. IF THERE ARE ANY QUESTIONS PLEASE | | | CALL (561) 659-8096 EXT 8372/8451 |
|