| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | MECH REMOVED FROM PRIMEDENIED******* | | | 1) PROVIDE SHAFT DETAIL FOR PROJECTOR | | | EXHAUST SYSTEMS | | | 2) PROVIDE INFORMATION ON CODE REQUIRED | | | BACKDRAFT DAMPERS FOR EXHAUST FANS | | | 3) PROJECTOR EXHAUST DUCT DETAIL SHOWS | | | FLEXABLE METAL DUCT. 1997 SBC 403.3.8.1 | | | DOES NOT ALLOW FLEX DUCT EXCEPT AT CONN- | | | ECTION TO PROJECTOR | | | 4) VARIABLE OCCUPANCY NOT ALLOWED FOR | | | THE THEATERS. 50% REDUCTION IS NOT A | | | REALISTIC EXPECTATION FOR OCCUPANCY FOR | | | THIS PROJECT | | | 5) LOCAL CODE REQUIRES 18" MIN. CLEARANC | | | BETWEEN ROOF SURFACE AND BOTTOM OF SUPP- | | | ORT STRUCTURE FOR CONDENSING UNITS | | | 6) PROVIDE DETAIL FOR SHAFT ENCLOSURES | | | TO SHOW COMPLIANCE WITH 1997 SMC AND | | | NFPA 96 | | | 7) PROVIDE SEQUENCE OF OPERATION FOR | | | ATRIUM EXHAUST SYSTEM | | | 8) PROVIDE LOCATION AND ACCESS TO DUCT | | | SMOKE DETECTORS TO SHOW COMPLIANCE WITH | | | 1997 SMC AND NFPA 90A | | | 9) PROVIDE AIR BALANCE SCHEDULE FOR | | | BUILDING TO SHOW COMPLIANCE WITH 1997 | | | SMC 501.2 | | | ABOVE INFORMATION REQUIRED TO PROVIDE | | | REVIEW OF THIS PROJECT. INSUFFICIENT | | | INFORMATION INCLUDED FOR REVIEW |
|