Plan Review Notes
Plan Review Notes For Permit 00020337
Permit Number 00020337
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00MECH REMOVED FROM PRIMEDENIED*******
 1) PROVIDE SHAFT DETAIL FOR PROJECTOR
 EXHAUST SYSTEMS
 2) PROVIDE INFORMATION ON CODE REQUIRED
 BACKDRAFT DAMPERS FOR EXHAUST FANS
 3) PROJECTOR EXHAUST DUCT DETAIL SHOWS
 FLEXABLE METAL DUCT. 1997 SBC 403.3.8.1
 DOES NOT ALLOW FLEX DUCT EXCEPT AT CONN-
 ECTION TO PROJECTOR
 4) VARIABLE OCCUPANCY NOT ALLOWED FOR
 THE THEATERS. 50% REDUCTION IS NOT A
 REALISTIC EXPECTATION FOR OCCUPANCY FOR
 THIS PROJECT
 5) LOCAL CODE REQUIRES 18" MIN. CLEARANC
 BETWEEN ROOF SURFACE AND BOTTOM OF SUPP-
 ORT STRUCTURE FOR CONDENSING UNITS
 6) PROVIDE DETAIL FOR SHAFT ENCLOSURES
 TO SHOW COMPLIANCE WITH 1997 SMC AND
 NFPA 96
 7) PROVIDE SEQUENCE OF OPERATION FOR
 ATRIUM EXHAUST SYSTEM
 8) PROVIDE LOCATION AND ACCESS TO DUCT
 SMOKE DETECTORS TO SHOW COMPLIANCE WITH
 1997 SMC AND NFPA 90A
 9) PROVIDE AIR BALANCE SCHEDULE FOR
 BUILDING TO SHOW COMPLIANCE WITH 1997
 SMC 501.2
 ABOVE INFORMATION REQUIRED TO PROVIDE
 REVIEW OF THIS PROJECT. INSUFFICIENT
 INFORMATION INCLUDED FOR REVIEW