Plan Review Notes
Plan Review Notes For Permit 00020337
Permit Number 00020337
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001- MAIN SWITCH GEAR ROOM NEEDS TO COMPLY
 WITH 110-16 FOR WORKING CLEARANCES,
  
 2- ROOM MEETS CODE BUT IF SOMETHING IS
 ADDED OR MOVED IT COULD BECOME A
 PROBLEM.
  
 3- PAGE E-14 TRANSFER SWITCH HAS NO DISC
 ON THE LINE SIDE IN THE GEAR ROOM.
 MAINS ARE TO BE GROUPED ONE ON THE
 1ST AND THE REST ON THE SECOND IS TO
 REMOTE.