Plan Review Notes
Plan Review Notes For Permit 00020273
Permit Number 00020273
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:001)THE MINIMUM NUMBER OF WATER CLOSETS
 REQD.FOR THE MALES BASED ON THE SQUARE
 FEET OF HABITABLE FLOOR SPACE,OCCUPANT
 LOAD AND TABLE 407 IS 4.(3 FOR THE FIRST
 150 PERSONS AND 1 FOR EACH ADDITIONAL
 100 PERSONS OR FRACTION THEREOF.)
  
 2)FOR THE FEMALES-BASED ON THE SAME
 DATA AND CRITERIA NOTED ABOVE,4 WATER
 CLOSETS ARE REQD.FOR THE FIRST 150
 PERSONS,AND 1.5 FOR EACH ADDITIONAL 100
 PERSONS OR FRACTION THEREOF WHICH BRINGS
 THE TOTAL NUMBER OF WATER CLOSETS REQD.
 FOR THE FEMALES TO 6.
  
 3)THE TOTAL NUMBER OF LAVATORIES REQD.
 FOR THE FEMALES IS 3 FOR THE FIRST 125
 PERESONS AND 1.5 FOR EACH ADDITIONAL
 120 PERSONS OVER 125 WHICH BRINGS THE
 TOTAL TO 5 LAVATORIES.
  
 ***NOTE:THESE REQS.ARE BASED UPON THE
 THE FLOOR AREA CALCULATIONS SUBMITTED BY
 COOPER CARRY DATED AUGUST 23,2000.
 CALCULATIONS SHALL BE SUBMITTED FOR THE
 DEDUCTED AREAS USED TO ARRIVE AT THE
 PRESENT FIGURES.SEE SPC SEC.407.1.2.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.