Plan Review Notes For Permit 00020273
Permit Number 00020273
Review Stop E
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PREVIOUS NOTES WERE NOT ADDRESS-
 -ED. PLEASE NOTE THAT ALL REVISED PANEL
 SCHEDULES AND LOAD CALCUALTIONS ARE TO
 BE SIGNED AND SEALED BY ENGINEER OF
 RECORD.REVISED LOAD CALCS AND PANELS
 WERE FAXED. THIS IS WILL NOT BE ACCEPTED
 THIS IS A STATE STATUE.
  
 2)NOTE:PLEASE SUBMIT ELECTRICAL ROOM
 DIMENSIONS. SHOW FOR ELECTRICAL CLEAR-
 -ENCES FOR TRANFORMER AS PER 450-21
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. PLANS THAT ARE SUBMITTED
 ARE TO BE ATTACHED BY CONTRACTOR.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372