| Plan Review Notes For Permit 00020273 |
| Permit Number |
00020273 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PREVIOUS NOTES WERE NOT ADDRESS- | | | -ED. PLEASE NOTE THAT ALL REVISED PANEL | | | SCHEDULES AND LOAD CALCUALTIONS ARE TO | | | BE SIGNED AND SEALED BY ENGINEER OF | | | RECORD.REVISED LOAD CALCS AND PANELS | | | WERE FAXED. THIS IS WILL NOT BE ACCEPTED | | | THIS IS A STATE STATUE. | | | | | | 2)NOTE:PLEASE SUBMIT ELECTRICAL ROOM | | | DIMENSIONS. SHOW FOR ELECTRICAL CLEAR- | | | -ENCES FOR TRANFORMER AS PER 450-21 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. PLANS THAT ARE SUBMITTED | | | ARE TO BE ATTACHED BY CONTRACTOR. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|