| Plan Review Notes For Permit 00020273 |
| Permit Number |
00020273 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: AS PER OUR CONVERSATION. SHOWING | | | THE PANEL WITH FEED-THRU LUGS WAS FINE. | | | STILL NEED TO SHOW THE LOAD CALCULATIONS | | | COMPLETED AT THE BOTTOM OF EACH PANEL. | | | LIGHTING TO BE SHOWN AT 125 % | | | | | | 2)NOTE: FILL IN OUTLETS PER LOCAL CODE. | | | | | | 3)NOTE: PLEASE SEE ART 450-21-B FOR | | | TRANSFORMER REQ`MENTS. PLEASE GIVE EXACT | | | DIMENSIONS OF ELETRICAL ROOM WITH VERT. | | | AND HORIZONTALCLEARENCES. OO | | | | | | 4)NOTE: PLEASE COMPLETE THE LOAD CALCU- | | | LATION FOR LOAD ON MAIN "H". | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 |
|