Plan Review Notes
Plan Review Notes For Permit 00020264
Permit Number 00020264
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** PROVISO ****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 NEW MAIN DISC. BEING INSTALLED. MUST BE
 RATED TO HANDLE THE AVAILABLE FAULT
 CURRENT. AS PER 110-9/110-10
  
 2)NOTE: PLEASE CHECK THE EQUIPMENT SCHED
 -ULE ON E-2 TO CORRELATE WITH THE PANEL
 SCHEDULE ON E-3.
  
 3)NOTE: PLEASE SHOW THE LOAD CALCULATION
 FOR THE MAIN PANEL"H". 215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL BEFORE THE
 ROUGH ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372