| Plan Review Notes For Permit 00020264 |
| Permit Number |
00020264 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** PROVISO **************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | NEW MAIN DISC. BEING INSTALLED. MUST BE | | | RATED TO HANDLE THE AVAILABLE FAULT | | | CURRENT. AS PER 110-9/110-10 | | | | | | 2)NOTE: PLEASE CHECK THE EQUIPMENT SCHED | | | -ULE ON E-2 TO CORRELATE WITH THE PANEL | | | SCHEDULE ON E-3. | | | | | | 3)NOTE: PLEASE SHOW THE LOAD CALCULATION | | | FOR THE MAIN PANEL"H". 215-5 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL BEFORE THE | | | ROUGH ELECTRICAL INSPECTION IS CALLED IN | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|