| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-TRUSS DRAWINGS SUBMITTED ARE FOR |
| | ANOTHER MODEL. |
| | -THERE IS ANOTHER SET OF TRUSS DRAWINGS |
| | ON FILE, SIGNED AND SEALED BY ANOTHER |
| | ENGINEER. CLARIFY. |
| | 2-SEE ITEMS REQUESTED ON PREVIOUS |
| | PROVISO. |
| | 3-GARAGE DOOR DESIGN PRESSURES: |
| | -LETTER BY ARCHITECT IS NOT CLEAR. |
| | THERE ARE TWO DIFFERENT SIZES OF DOORS |
| | THEREFORE, DESIGN PRESSURES SHOULD BE |
| | DIFFERENT. PROVIDE CALCULATIONS FOR |
| | EACH OPENING. |
| | -SUBMIT PRODUCT APPROVAL FOR EACH TYPE |
| | OF DOOR. THERE IS NONE WITH THE SET. |
| | 4-SLIDING GLASS DOORS WITH TRANSOM ABOVE |
| | SITE SPECIFIC PRODUCT APPROVAL NEEDS |
| | THE PROFESSIONAL OF RECORD (KUNIK) TO |
| | SIGN, SEAL AND DATE THE SEPARATE |
| | PRODUCT APPROVAL FORM. PLEASE INCLUDE |
| | ALL REQUIRED INFORMATION FOR THE |
| | SPECIFIC JOB AND ALL INFORMATION |
| | REQUIRED BY THE PROFESSIONALS OF |
| | RECORD TO AVOID UNNECESSARY RETURNS |
| | AND DELAYS. |
| | 5-ENTRY DOORS PRODUCT APPROVAL: |
| | -ENGINEER WHO SIGNED AND SEALED THE |
| | DOCUMENT IS NOT THE PROFESSIONAL OF |
| | RECORD (IS KUNIK). |
| | 6-ROYAL PALM ALUMINUM LETTER FROM |
| | MANAGER OF ENGINEERING TO BE SIGNED, |
| | SEALED AND DATED. |
| | |
| | |
| | |
| | NOTE: |
| | ENGINEERS TO PROVIDE ALL INFORMATION |
| | REQUIRED BY PROFESSIONAL ENGINEERS WHEN |
| | SEALING A DOCUMENT FOR PUBLIC RECORD. |