Plan Review Notes
Plan Review Notes For Permit 00011426
Permit Number 00011426
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00REVISIONS APPROVED WITH PROVISO:
 1-CLARIFY WHO IS THE ENGINEER OF RECORD
 FOR THIS HOUSE. THERE ARE TOO MANY
 ENGINEERS INVOLVED IN THIS PROJECT.
 -THE STRUCTURAL ENGINEER WHO SIGNED THE
 ORIGINAL PACKAGE SUBMITTED WAS DR.
 ERNEST A. KUONEN P.E.. NOW HE DIDN'T
 SIGNED AND SEALED THESE DWGS. WHY?
 -THE DESIGN CERTIFICATION FOR BUILDING
 CODE COMPLIANCE FORM IS SIGNED AND
 SEALED BY ROBERT E. AGSTEN III. P.E.
 -AND, THE PRODUCT APPROVAL IS SIGNED
 BY WHO?
 2-PRODUCT APPROVAL FOR ENTRY DOORS NEED:
 -ITEM #8: A)ADDRESS OF ENGINEER. B)DATE
 THAT DOCUMENT WAS SIGNED AND SEALED.
 C) NEED A WET SIGNATURE NO A COPY.
 -ITEM #9: A)CLEARLY PROVIDE NAME AND
 ADDRESS OF ENGINEER OF RECORD FOR THIS
 PROJECT.
 3-PROVIDE PRODUCT APPROVAL FOR ARCHED
 WINDOWS.
 4-IF ENGINEER OF RECORD IS DR. KUONEN
 P.E. THEN HE NEEDS TO SIGN SEAL AND
 DATE ALL STRUCTURAL DRAWINGS AND
 THE DESIGN CERTIFICATION CERTIFICATION
 FOR BUILDING CODE COMPLIANCE FORM AS
 WELL.
 NOTE: CLEARLY INDICATE NAME, ADDRESS
 AND LICENSE # IN EVERY DOCUMENT
 PREPARED BY THE ENGINEER.
 5-GARAGE DOORS:
 -DESIGN PRESSURES ARE LOWER THAN THE
 DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT OR ENGINEER OF RECORD.