| 2001-01-08 00:00:00 | REVISIONS APPROVED WITH PROVISO: |
| | 1-CLARIFY WHO IS THE ENGINEER OF RECORD |
| | FOR THIS HOUSE. THERE ARE TOO MANY |
| | ENGINEERS INVOLVED IN THIS PROJECT. |
| | -THE STRUCTURAL ENGINEER WHO SIGNED THE |
| | ORIGINAL PACKAGE SUBMITTED WAS DR. |
| | ERNEST A. KUONEN P.E.. NOW HE DIDN'T |
| | SIGNED AND SEALED THESE DWGS. WHY? |
| | -THE DESIGN CERTIFICATION FOR BUILDING |
| | CODE COMPLIANCE FORM IS SIGNED AND |
| | SEALED BY ROBERT E. AGSTEN III. P.E. |
| | -AND, THE PRODUCT APPROVAL IS SIGNED |
| | BY WHO? |
| | 2-PRODUCT APPROVAL FOR ENTRY DOORS NEED: |
| | -ITEM #8: A)ADDRESS OF ENGINEER. B)DATE |
| | THAT DOCUMENT WAS SIGNED AND SEALED. |
| | C) NEED A WET SIGNATURE NO A COPY. |
| | -ITEM #9: A)CLEARLY PROVIDE NAME AND |
| | ADDRESS OF ENGINEER OF RECORD FOR THIS |
| | PROJECT. |
| | 3-PROVIDE PRODUCT APPROVAL FOR ARCHED |
| | WINDOWS. |
| | 4-IF ENGINEER OF RECORD IS DR. KUONEN |
| | P.E. THEN HE NEEDS TO SIGN SEAL AND |
| | DATE ALL STRUCTURAL DRAWINGS AND |
| | THE DESIGN CERTIFICATION CERTIFICATION |
| | FOR BUILDING CODE COMPLIANCE FORM AS |
| | WELL. |
| | NOTE: CLEARLY INDICATE NAME, ADDRESS |
| | AND LICENSE # IN EVERY DOCUMENT |
| | PREPARED BY THE ENGINEER. |
| | 5-GARAGE DOORS: |
| | -DESIGN PRESSURES ARE LOWER THAN THE |
| | DESIGN PRESSURES CALCULATED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD. |