| Permit Number |
00011426 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | | 1-UPDATE/REVISE ALL DRAWINGS AS REQUIRED | | | SEE COMMENTS ON PLANS. | | | 2-DRAWING A2: WHERE IS COLUMN C6. | | | 3-ENTRY DOOR TO HAVE 32" MINIMUM CLEAR | | | OPENING. TABLE 1004 SBC 1997. | | | 4-PROVIDE THE DESIGN PRESSURES AT ALL | | | EXTERIOR OPENINGS. SEC. 1606 SBC 1997. | | | 5-SPECIFY CEILING INSTALLATION AT ENTRY | | | AND REAR PORCHES. SPECIFY FASTENERS | | | AND SPACING. SEC. 2504.2 SBC 1997. | | | 6-PRODUCT APPROVAL FOR ENTRY DOORS IS | | | FOR OUTSWING DOORS. ARCHITECT'S PLANS | | | SHOWS INSWING DOORS. PROVIDE PRODUCT | | | APPROVAL FOR INSWING DOORS OR REVISE | | | ARCHITECT'S DRAWINGS. | | | 7-REVISE ENGINEERED ROOF TRUSSES. THERE | | | IS ONLY ONE MEAN ROOF HEIGHT FOR | | | ENTIRE BUILDING. MEAN ROOF HEIGHT IS | | | TAKEN FROM GRADE, NOT FROM FINISH | | | FLOOR, TO THE AVERAGE POINT OF HIGHEST | | | ROOF. IN THIS CASE IS PLUS OR MINUS | | | 20'-0". SEE EXTERIOR ELEVATIONS. | | | 8-REVISE THE DESIGN CERTIFICATION FOR | | | BUILDING CODE COMPLIANCE FORM. MEAN | | | ROOF HEIGHT IS PLUS OR MINUS 20'-0". | | | SEE EXTERIOR ELEVATIONS. |
|