| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF ALL | | | EQUIPMENT MAINS/PANEL. AS REQ`D BY | | | ARTS 110-9/110-10. /215-5 OF THE NEC. | | | | | | 2)NOTE: SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE ALL SLEEPING ROOMS. | | | | | | 3)NOTEL PLEASE LIST THE DEDICATED BATH(S | | | CIRCUT REQ`D BY 210-52D.SHALL BE #12 AND | | | 20 AMP. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW AND APPROVAL. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 | | | EXT 8372 |
|