| Plan Review Notes For Permit 00011376 |
| Permit Number |
00011376 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** PROVISO ***************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS. AIC RATING NEED TO BE | | | ABLE TO HANDLE AVAILABLE FAULT CURRENT | | | AT MAINS. AIC RATING CAN BE FIGURED FROM | | | FAULT CURRENT CALCULATIONS. AS PER | | | ARTS:110-9/110-10/215-5 | | | | | | 2)NOTE:PLEASE HAVE REQ`D BATH(S) CURCUT | | | (S) LISTED ON PANEL SCHEDULE AS REQ`D BY | | | ART:210-52D OF THE NEC. NEEDS TO BE | | | 20AMP AND #12 AWG. REMEMBER THAT THERE | | | STILL MUST BE TWO SPARE SPACES IN THE | | | PANEL. YOU SHOW RANGE AS BEING ONE | | | SPACE.PLEASE CHE3CK FOR SIZE OF PANEL. | | | | | | 3)NOTE:AS REQ`D BY 1993/1996 NFPA-72 | | | CHAPTER 2-2.1.1.1 SMOKE DETECTORS ARE | | | REQ`D INSIDE AND OUTSIDE ALL SLEEPING | | | ROOMS. PLEASE SHOW ON RESUBMITTED | | | DRAWINGS. | | | | | | PLEASE HAVE ALL THE ABOVE INFORMATION | | | SUBMITTED FOR REVEIW AND APPROVAL BEFORE | | | FIRST ROUGH ELECTRICAL INSPECTION IS | | | CALLED IN. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|