Plan Review Notes
Plan Review Notes For Permit 00011376
Permit Number 00011376
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 EQUIPMENT MAINS. AIC RATING NEED TO BE
 ABLE TO HANDLE AVAILABLE FAULT CURRENT
 AT MAINS. AIC RATING CAN BE FIGURED FROM
 FAULT CURRENT CALCULATIONS. AS PER
 ARTS:110-9/110-10/215-5
  
 2)NOTE:PLEASE HAVE REQ`D BATH(S) CURCUT
 (S) LISTED ON PANEL SCHEDULE AS REQ`D BY
 ART:210-52D OF THE NEC. NEEDS TO BE
 20AMP AND #12 AWG. REMEMBER THAT THERE
 STILL MUST BE TWO SPARE SPACES IN THE
 PANEL. YOU SHOW RANGE AS BEING ONE
 SPACE.PLEASE CHE3CK FOR SIZE OF PANEL.
  
 3)NOTE:AS REQ`D BY 1993/1996 NFPA-72
 CHAPTER 2-2.1.1.1 SMOKE DETECTORS ARE
 REQ`D INSIDE AND OUTSIDE ALL SLEEPING
 ROOMS. PLEASE SHOW ON RESUBMITTED
 DRAWINGS.
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVEIW AND APPROVAL BEFORE
 FIRST ROUGH ELECTRICAL INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372