| 2001-01-08 00:00:00 | PLANS SHALL BE SEALED BY THE |
| | DESIGN PROFESSIONAL OF RECORD PER |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.3 |
| | |
| | DRINKING FOUNTAINS SHALL COMPLY W/FACBC |
| | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE |
| | MADE FOR PEOPLE WHO USE WHEELCHAIRS AND |
| | FOR THOSE WHO HAVE TROUBLE BENDING OR |
| | STOOPING.INDICATE MEANS OF COMPLIANCE ON |
| | PLANS. |
| | |
| | INDICATE OCCUPANT LOAD ON PLANS FOR |
| | DETERMINATION OF MINIMUM SANITARY REQS. |
| | SEE SPC SEC.407.1.3.FOR ALLOWED DEDUCT- |
| | IBLE AREAS AND COMPLY W/SPC TABLE 407. |
| | (PLUMBING FIXTURES ARE NOT ADEQUATE FOR |
| | SPECIFIED OCCUPANT LOAD.) |
| | |
| | URINAL SHALL BE LOCATED TO ENSURE USER |
| | PRIVACY PER SPC SEC.404.3.(FIXTURE IS |
| | LOCATED IN LINE OF SIGHT FROM CORRIDOR.) |
| | |
| | WET VENTS SHALL RECEIVE THE DISCHARGE |
| | FROM FIXTURE DRAINS ONLY PER COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.911.1.1. |
| | |
| | DRY VENTS NOT PERMITTED PER SPC SEC. |
| | 901.2,906.2. |
| | |
| | CLARIFY TERMINATION PT.OF RELIEF DRAIN |
| | FOR EWH.PLANS NOTE TO EXTERIOR AND ALSO |
| | TO MOP SINK.EITHER IS ACCEPTABLE PER SPC |
| | |
| | CLEANOUTS ARE REQD.IN HORIZONTAL |
| | DRAINAGE PIPE PER SPC SEC.710.2.1. |