| 2001-01-08 00:00:00 | URINAL SHALL COMPLY W/FACBC SEC.4.18.2 |
| | THRU 4.18.4 |
| | |
| | WATER SUPPLY CONTROL SHALL COMPLY W/ |
| | SPC SEC.610.4.1,610.4.2. |
| | |
| | DRINKING FOUNTAIN ON 1ST.FLR.SHALL BE |
| | ACCESSIBLE TO THE PUBLIC PER SPC SEC. |
| | 407.2.2.AND COMPLY W/FACBC SEC.4.15. |
| | |
| | SUBMIT A SANITARY RISER DIAGRAM THAT |
| | COMPLIES W/THE STANDARD PLUMBING CODE. |
| | |
| | WATER HEATER SHALL BE READILY ACCESSIBLE |
| | PER SPC SEC.501.7.(SUPPLY A PERMANENT |
| | LADDER OR RELOCATE EWH TO FLOOR.)++ |
| | |
| | T & P VALVE DRAIN SHALL DISCHARGE TO |
| | EXTERIOR PER COUNTYWIDE AMENDMENTS TO |
| | SPC SEC.507.8.4. |
| | |
| | ALL PUBLIC AND COMMON USE AREA TOILET |
| | ROOMS SHALL COMPLY W/FACBC SEC.4.1.3(11) |
| | |
| | CLEARLY SHOW DIMENSIONS (L X W) OF |
| | HANDICAP TOILET STALLS.COMPLY W/FACBC |
| | SEC.4.17.3 EXCEPTION :NEW CONSTRUCTION. |
| | |
| | DRINKING FOUNTAIN ON 2ND.FLR.SHALL |
| | COMPLY W/FACBC SEC.4.1.3.(10)(A) |
| | |
| | WATER HEATERS SHALL BE EQUIPPED W/PANS |
| | AND DRAINS PER COUNTYWIDE AMENDMENTS TO |
| | SPCSEC.507.8.1,507.8.3. |
| | |
| | CLARIFY USE OF ROOM CONTAINING DOUBLE |
| | SINK.IF THIS ROOM IS A BREAKROOM THE |
| | SINK SHALL COMPLY W/FACBC SEC.4.24.1- |
| | 4.24.7. |
| | |
| | CLEARLY SIZE ALL VENTS ON SANITARY RISER |
| | COMPLY W/SPC TABLE 920.2,920.4. |
| | |
| | VENTING OF WATER CLOSETS SHALL COMPLY W/ |
| | SPC SEC.906.2.1.,906.2.2. |