| Plan Review Notes For Permit 00011297 |
| Permit Number |
00011297 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************DENIED********************* | | | | | | 1) AIR BALANCE REQUESTED NOT PROVIDED: | | | OUTSIDE AIR PROVIDED ON PLAN EQUALS | | | 4955 CFM | | | LESS BATH EXHAUST OF 200 CFM = 4755 CFM | | | LESS 4952 CFM RELIEF VENTILATOR=-197CFM | | | WHICH WOULD PUT BUILDING IN A NEGATIVE | | | PRESSURE. | | | PROVIDE CORRECTED AIR BALANCE SHOWING | | | OUTSIDE AIR AND EXHAUST AIR BALANCE, | | | INCLUDING EXFILTRATION, RELIEF AND | | | EXHAUST AIR FIGURES. |
|