2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: STILL NEED TO SHOW GROUNDING
 SYSTEM ON THE LINESIDE OF TRANSFORMER.
 215-5
 2)NOTE:PLEASE MAKE NOTES ON PLANS THAT
 COLOR CODING FOR FEEDERS ARE TO BE TO
 LOCAL CODE.215
  
 3)NOTE:PLEASE INDICATE ON PLANS ALL LOAD
 -S THAT ARE CONTINUOUS AT 125%.
 SHOW IN LOAD CALCULATION FOR ALL
 LIGHTING.ALSO MOTOR LOAD FOR THE TWO
 CLOCK MOTORS.AND ANY OTHER LOADS.
 215-5/220-12/210-19A
  
 4)NOTE: ALSO FOR 210-62 REQ`MENTS FOR
 OUTLETS IN SHOW WINDOWS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS PLEASE
 CALL 561-659-8096 EXT 8372