| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1. FLORIDA ENERGY SHEETS REQUIRED. | | | | | | 2. NOTES ADDED TO DRAWINGS MUST BE | | | APPROVED BY THE DESIGNER OF RECORD. | | | SEE SHEETS, A-0, A-0.1, A-1.2, A-4.0, | | | A-6.1, A-6.2, A-6.3, A-6.4, 3-3.0 AND | | | E-3.1. | | | | | | 3. SHEET A-6.4 PLANS DO NOT INDICATE | | | CODE COMPLIANCE FOR MISSLE IMPACT | | | PROTECTION. SEE 1997 STANDARD BUILDING | | | CODE AND CITY OF WEST PALM BEACH | | | AMENDMENTS (SSTD 12-97). | | | | | | 4. SHEET A-12 SECTION, N & N1 INDICATE | | | CONSTRUCTION OF ONLY ONE SIDE OF FIRE | | | SEPERATION. CITY POLICY REQUIRES | | | CONSTRUCTION OF BOTH SIDES OF THE WALL | | | REVISE NOTES AND SECTION. | | | | | | 5. FIRE SPRINKLER CONTRACTOR MUST APPLY | | | FOR A FIRE SPRINKLER PERMIT. |
|