| Plan Review Notes For Permit 00011297 |
| Permit Number |
00011297 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CITY PLACE APPROVAL REQD.ON PLANS. | | | | | | SHT.A-0-THE ADOPTED PLBG.CODE IS | | | STANDARD PLUMBING CODE 1994 EDITION. | | | | | | SHT.A-5.3-SHOW MOUNTING HEIGHTS AND | | | FIXTURE CLEARANCES OF PLUMBING FIXTURES | | | AND ACCESSORIES.COMPLY W/FACBC. | | | | | | SHOW TURNING SPACE FOR WHEELCHAIR IN | | | TOILET ROOMS PER FACBC SEC.4.2.3. | | | | | | MINIMUM TOILET FACILITIES SHALL COMPLY | | | W/SPC SEC.407.1.4. | | | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | | SEC.610.4.1. | | | | | | A DRINKING FOUNTAIN IS REQD.ON THE 1ST. | | | AND SECOND FLOOR PER SPC TABLE 407. | | | | | | A VENT SHALL BE LOCATED BETWEEN THE TWO | | | WATER CLOSETS AND COMPLY W/COUNTYWIDE | | | AMENDMENTS TO SPC SEC.911.1.3. | | | | | | WATER HEATER SHALL BE READILY ACESSIBLE | | | PER SPC SEC.501.7.(A PERMANENTLY | | | INSTALLED LADDER IS REQD.OR RELOCATE | | | EWH TO FLOOR.) | | | | | | T & P VALVE DRAIN TERMINATION SHALL | | | COMPLY W/COUNTYWIDE AMENDMENTS TO SPC | | | SEC.507.8.4. |
|