Plan Review Notes For Permit 00011297
Permit Number 00011297
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CITY PLACE APPROVAL REQD.ON PLANS.
  
 SHT.A-0-THE ADOPTED PLBG.CODE IS
 STANDARD PLUMBING CODE 1994 EDITION.
  
 SHT.A-5.3-SHOW MOUNTING HEIGHTS AND
 FIXTURE CLEARANCES OF PLUMBING FIXTURES
 AND ACCESSORIES.COMPLY W/FACBC.
  
 SHOW TURNING SPACE FOR WHEELCHAIR IN
 TOILET ROOMS PER FACBC SEC.4.2.3.
  
 MINIMUM TOILET FACILITIES SHALL COMPLY
 W/SPC SEC.407.1.4.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1.
  
 A DRINKING FOUNTAIN IS REQD.ON THE 1ST.
 AND SECOND FLOOR PER SPC TABLE 407.
  
 A VENT SHALL BE LOCATED BETWEEN THE TWO
 WATER CLOSETS AND COMPLY W/COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.3.
  
 WATER HEATER SHALL BE READILY ACESSIBLE
 PER SPC SEC.501.7.(A PERMANENTLY
 INSTALLED LADDER IS REQD.OR RELOCATE
 EWH TO FLOOR.)
  
 T & P VALVE DRAIN TERMINATION SHALL
 COMPLY W/COUNTYWIDE AMENDMENTS TO SPC
 SEC.507.8.4.