| Plan Review Notes For Permit 00011297 |
| Permit Number |
00011297 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1. CITYPLACE APPROVAL STAMP NOT ON PLANS | | | 2. SHEET A-0, CODE REFERENCES NOT | | | CORRECT, | | | MECHANICAL CODE IS 1997 NOT 1996 SBC | | | PLUMBING CODE IS 1994 NOT 1997 SBC | | | | | | KEY PLAN IS NOT INDICATING PROPER | | | LOCATION FOR UNIT. | | | UNIT ADDRESS LISTED IS NOT APPROVED FOR | | | USE BY CITY OR US POSTAL SERVICE. | | | 3. SHEET A-1.2 MEZZAINE NOT IN | | | COMPLIANCE WITH 1997 SBC SECTIONS 7, 10, | | | AND 11ALSO CHAPTER 16 FOR LOAD | | | INFORMATION. | | | 4. ESCULATORS SHALL COMPLY WITH CHAPTER | | | 7, 10 AND 30, 1997 SBC. | | | 5. SIGNS AND FIGURES REQUIRE SEPERATE | | | PERMITTING. | | | 6. SHEET A-6.4 PROVIDE PRODUCT APPROVALS | | | FOR ALL EXTERIOR WINDOWS AND DOORS, SEE | | | NOTE 24. | | | 7.ALL WOOD SHAL BE PRESSURE TREATED FIRE | | | RETARDANT LUMBER SBC 1997 SECTION707. | | | 8. SHEET A-03(3)&(4) INDICATE CHANGE IN | | | FLOOR ELEVATIONS, PROVIDE INFORMATION | | | ON PLAN INDICATING COMPLIANCE WITH 1997 | | | FL. HANDICAPPED CODE. | | | 9. INDICATE THE TOTAL HEIGHT OF | | | CONSTRUCTION ON PLANS. | | | PLAN REVIEW NOTES 1/28/00 | | | 10. DEMISING WALL SECOND FLOOR TO BE | | | 2 HOUR SEE TABLE 704.1 SEPERATION | | | ASSEMBLY TO MERCANTILE. |
|