Plan Review Notes For Permit 00011238
Permit Number 00011238
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SHOW DIMENSIONS OF SHOWER(LXW).SHOWER
 SHALL BE A MIN.OF 30"WIDE AND 1024 SQ.IN
 OF FLOOR AREA.PER COUNTYWIDE AMENDMENTS
 TO SPC SEC.409.8.2.1.
  
 LOCATION OF PLBG.FIXTURES ON SANITARY
 RISER SHALL CORRELATE W/FLOOR PLAN PER
 COUNTYWIDE AMENDMENTS TO SPC 104.2.1.
  
 TUB AND SHOWER NOT PROPERLY VENTED PER
 SPC SEC.901.2.