Plan Review Notes
Plan Review Notes For Permit 00011238
Permit Number 00011238
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATION
 FOR THE ENTIRE SERVICE. YOU SHOW SERVICE
 SIZE...ADDITIONAL 80 AMPS??? IS THIS
 THE TOTAL LOAD ON HOUSE? IF SO PLEASE
 SHOW.INCLUDE SERVICE CONDUCTOR SIZES.
  
 2)NOTE: PLEASE THE REQ`MENTS FOR THE
 DEDICATED BATH(S) CIRCUT(S) AS PER ART:
 210-52D THEY ARE TO BE 20 AMP AND #12AWG
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372