| Plan Review Notes For Permit 00011168 |
| Permit Number |
00011168 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** PROVISO****************** | | | | | | 1)NOTE:AS REQ`D BY 210-8-A-6 ALL OUTLETS | | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | | GFI/GFI PROTECTED. | | | | | | 2)NOTE: NEED TO SHOW EXISTING SERVICE | | | SIZE AND NEW LOAD CALCULATION. NEW A/C | | | IS BEING ADDED AND TOTAL LOAD NEEDS TO | | | BE SHOWN. | | | | | | 3)NOTE: PLEASE SHOW NEW CONDENSING UNIT | | | LOCATION WITH DISC. 440-11 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL BEFORE ROUGH | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL 659-8096 EXT | | | 8372 |
|