| 2001-01-24 00:00:00 | 1) THE PLAN DOES NOT REFLECT THE | | | LOCATION OF THE REAR EXIT FOR THE | | | RESTAURANT. WILL THE LOCATION OF THE | | | NEW DUMPSTER ENCLOSURE BLOCK THE | | | OPENING OF THE DOOR. | | | 2) SITE PLAN DOES NOT REFLECT EXIT DOOR | | | LOCATIONS FOR THE NEW WAREHOUSE. | | | 3) A SET OF DOUBLE DOORS ON THE | | | FOUNDATION PLAN ARE NOT INDICATED TO | | | BE 1 1/2 FIRE RATED. THEY APPEAR TO BE | | | LOCATED IN A TWO HOUR FIRE WALL. | | | 4) PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS. A SEPARATE PERMIT IS REQUIRED. | | | 5) THE SMOKE DETECTOR INSTALLED ON THE | | | CEILING IS WHAT TYPE. IS IT ELECTRIC, | | | BATTERY OR TIED INTO THE FIRE ALARM | | | SYSTEM. | | | 6) WHAT WILL BE STORED IN THE WAREHOUSE. | | | 7) DOES EXITING FROM THE RETAIL STORE | | | ENTER INTO THE NEW WAREHOUSE BEFORE | | | REACHING THE EXTERIOR OF THE BUILDING. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|