Plan Review Notes
Plan Review Notes For Permit 00011143
Permit Number 00011143
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) NO EMERGENCY LIGHTING EQUIPMENT
 SHOWN.
 2) CLEARLY INDICATE EXIT LOCATIONS.
 3) WHY IS AN EXIT DOOR SHOWN LEADING
 PERSONS THROUGH STORAGE ROOM.
 4) WHAT IS THE MANUAL FIRE ALARM BOX
 CONNECTED TO.
 5) THE ROUND CIRCLES WITH SD WITHIN THEM
 INDICATES WHAT.
 6) EXIT DISCHARGE LOCATIONS NOT
 CLEARLY DEFINED.
 7) NO INTERIOR FINISH INFORMATION ON
 PLANS.
 8) EXIT DOORS AND HARDWARE ARE TO BE
 SHOWN.
 9) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910