| 2001-01-08 00:00:00 | *************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE SIGN AND SEAL PLANS PER |
| | FL. ADMINISTRATIVE CODES AND STATE STAT- |
| | -UES. 61G15-23.002/ CHAPTER 471.025 |
| | |
| | 2)NOTE: PLEASE CORRELATE ELECTRICAL PLAN |
| | TO FOUNDATION PLAN. OUTLETS/ROOMS DO |
| | NOT MATCH.A-2 SHOWS FLOOR OUTLETS AND |
| | SWITCHED RECEPTS NOT SHOWN ON A-2. |
| | STORAGE AREA NOT SHOWN ON A-4?? |
| | |
| | 3)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | FOR NEW LOADS BEING ADDED. LOAD CALCS |
| | SHOWN ARE FOR NEW/OLD?? SHEET A-2 SHOWS |
| | NEW 150AMP SERVICE WHICH IS NOT SHOWN ON |
| | A-4?? |
| | |
| | 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125%.(LIGHTING ETC). |
| | |
| | 5)NOTE: PLEASE SHOWS LOADS FOR TRACK |
| | LIGHTING SHOWN, PER 220-12B |
| | |
| | 6)NOTE: PLEASE SUBMIT PANEL SCHEDULES |
| | FOR NEW EQUIPMENT BEING INSTALLED. |
| | |
| | 7)NOTE: PLEASE SHOW OUTLET LAYOUT THAT |
| | CORRELATES TO FLOOR PLAN ON A-2. |
| | |
| | 8)NOTE: PLEASE CORRELATE LIGHITNG A-2 |
| | AND A-4 |
| | |
| | 9)NOTE: PLEASE CLARIFY LOADS SHOWN FOR |
| | HEAT. ??215-5 |
| | |
| | 10)NOTE: PLEASE SUBMIT MORE SPECS ON NEW |
| | EQUIPMENT BEING INSTALLED. 215-5 |
| | |
| | 11)NOTE: PLEASE SUBMIT AIC RATINGS FOR\\ |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BRKRS MUST BE RATED FOR THE |
| | AVAILABLE FAULT CURRENT PER 110-9 AND |
| | 110-10. SHOW PER 215-5. |
| | |
| | 12)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| | SYSTEM. EXISTING AND NEW. PLEASE NOTE |
| | PER 250-50 ALL NEW BLDG. STEEL AND COLD |
| | WATER PIPE TO HAVE GROUNDING ELECTRODE |
| | CONNECTION. |
| | |
| | |
| | 13)NOTE: PLEASE SEPARATE LOAD FOR NEW |
| | PANELS AND EXISTING.215-5 |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |