Plan Review Notes
Plan Review Notes For Permit 00011143
Permit Number 00011143
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SIGN AND SEAL PLANS PER
 FL. ADMINISTRATIVE CODES AND STATE STAT-
 -UES. 61G15-23.002/ CHAPTER 471.025
  
 2)NOTE: PLEASE CORRELATE ELECTRICAL PLAN
 TO FOUNDATION PLAN. OUTLETS/ROOMS DO
 NOT MATCH.A-2 SHOWS FLOOR OUTLETS AND
 SWITCHED RECEPTS NOT SHOWN ON A-2.
 STORAGE AREA NOT SHOWN ON A-4??
  
 3)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR NEW LOADS BEING ADDED. LOAD CALCS
 SHOWN ARE FOR NEW/OLD?? SHEET A-2 SHOWS
 NEW 150AMP SERVICE WHICH IS NOT SHOWN ON
 A-4??
  
 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%.(LIGHTING ETC).
  
 5)NOTE: PLEASE SHOWS LOADS FOR TRACK
 LIGHTING SHOWN, PER 220-12B
  
 6)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 FOR NEW EQUIPMENT BEING INSTALLED.
  
 7)NOTE: PLEASE SHOW OUTLET LAYOUT THAT
 CORRELATES TO FLOOR PLAN ON A-2.
  
 8)NOTE: PLEASE CORRELATE LIGHITNG A-2
 AND A-4
  
 9)NOTE: PLEASE CLARIFY LOADS SHOWN FOR
 HEAT. ??215-5
  
 10)NOTE: PLEASE SUBMIT MORE SPECS ON NEW
 EQUIPMENT BEING INSTALLED. 215-5
  
 11)NOTE: PLEASE SUBMIT AIC RATINGS FOR\\
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BRKRS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT PER 110-9 AND
 110-10. SHOW PER 215-5.
  
 12)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM. EXISTING AND NEW. PLEASE NOTE
 PER 250-50 ALL NEW BLDG. STEEL AND COLD
 WATER PIPE TO HAVE GROUNDING ELECTRODE
 CONNECTION.
  
  
 13)NOTE: PLEASE SEPARATE LOAD FOR NEW
 PANELS AND EXISTING.215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372