| Plan Review Notes For Permit 00011063 |
| Permit Number |
00011063 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | ALL NOTES PREVIOUSLY GIVEN!!! | | | | | | 1)NOTE:SHOW TWO CONDIUTS FROM METER TO | | | DISCS. YOU SHOW ONE GOING TO PANEL AND | | | ONE GOING TO ONE DISC.????? | | | | | | 2)NOTE:ART;210-52D WAS GIVEN FOR REF. | | | TO THE BATH CIRCUT REQ`MENTS. | | | SEE #12 AND 20 AMP REQ`D. | | | | | | 3)NOTE: AIC RATING OF MAINS REQ`D BY | | | 110-9/110-10 AND 215-5 | | | | | | 4)NOTE:MISSING SMOKE DETECTOR OUTSIDE | | | BEDROOM#2 | | | | | | ALSO NOTE IF PLUMB RISER IS ON PLANS | | | THEN THEY WILL HAVE TO BE REVIEWED. | | | | | | PLEASE MAKE THE ABOVE CHANGES AND IF | | | THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|