| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | | | | 1)NOTE: ALL NOTES FROM PREVIOUS REVIEWS | | | HAVE NOT BEEN ADDRESSED. PLEASE SEE | | | ALL NOTES ATTACHED. SHOW ALL BRANCH | | | CIRCUIT #`S ON PLANS!!!! AND CORRELATE | | | WITH PANEL SCHEDULE. | | | | | | 2)NOTE: LOAD CALCULATIONS HAVE BEEN | | | SUBMITTED, BUT ALL CONTINUOUS LOADS | | | TO BE SHOWN AT 125% (LIGHTING ETC) | | | LOAD CALCULATION SUBMITTED IS UNCLEAR. | | | YOU SHOW LOADS FOR FELLOWSHIP HALL AND | | | NEW SECOND FLOOR AREA. WHAT ABOUT EXIST- | | | -ING AREAS??? PLEASE CLARIFY | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|