| Plan Review Notes For Permit 00011046 |
| Permit Number |
00011046 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************************************** | | | | | | 1]ASSEMBLY OCCUPANCY REQUIRES TWO | | | SEPERATE AND REMOTE EXITS FROM EACH | | | STORY,SEE SECTIONS 1004.1.4AND1004.2, | | | ALSO 1001.1.3,1997 SBC. | | | 2]SHEET 3 SHOWS A DEAD END HALLWAY,20' | | | LONG NOT PERMITTED PER SECT.1005.2. | | | 3]PROVIDE DETAIL SPECIFYING OLD ROOF | | | JOIST/NEW FLOOR JOIST SIZE AND SPACING | | | LAYOUT. | | | 4]PLEASE CLERIFY PREFAB BEAM AND POST | | | COMMENT ON SHEET 4[EXISTING,NEW,BEARIN | | | POINTS]. | | | 5]CERTIFY ADDITIONAL LOADS IMPOSED ON | | | EXISTING ONE STORY CONSTRUCTION. |
|