| Date |
Text |
| 2001-01-08 00:00:00 | *****************PROVISO**************** |
| | REVISED PLUMBING SHEETS SHOWING ALL |
| | CORRECTIONS SHALL BE SUBMITTED FOR |
| | REVIEW PRIOR TO ISSUANCE OF PLUMBING |
| | PERMIT.ALL SHEETS SAHLL BE SIGNED AND |
| | SEALED PER FLA.STATUTE. |
| | |
| | SHOW SQ.FT.OF ROOF AREA DRAINED BY EACH |
| | DRAIN.COMPLY W/SPC SEC.1108.1,1108.2, |
| | 1108.3.INCLUDE 1/2 AREA OF VERTICAL WALL |
| | PER SPC SEC.1108.3. |
| | |
| | A PERMIT FOR THE DOMESTIC WATER AND FIRE |
| | SERVICE IS REQD.FROM THE DEPT.OF |
| | ENVIRONMENTAL PROTECTION.CONTACT PALM |
| | BEACH COUNT HEALTH DEPT.A PERMIT MAY |
| | ALSO BE REQD.FROM PALM BEACH COUNTY |
| | HEALTH DEPT.COUNTYWIDE AMENDMENTS TO |
| | SPC SEC.101.4.7. |
| | |
| | PLUMBING SHEETS SHOW DOMESTIC WATER |
| | SERVICE AS 3" AND CIVILS SHOW 2".CLARIFY |
| | |
| | FLOOR DRAINS ARE NOT PROPERLY VENTED. |
| | COMPLY W/SPC SEC.901.2. |
| | |
| | VENTS FOR WATER CLOSETS SHALL COMPLY W/ |
| | SPC SEC.920.2.(NO LESS THAN 1/2 THE |
| | DIAMETER OF THE DRAIN SERVED.) |
| | |
| | WATER HEATER ON 2ND FLOOR SHALL BE |
| | EQUIPPED W/PAN AND DRAIN PER COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.507.8.1. |
| | |
| | DRINKING FOUNTAINS ARE NOT SHOWN ON THE |
| | SANITARY OR WATER RISERS.COUNTYWIDE |
| | AMENBDMENTS TO SPC SEC.104.2.1. |