| 2001-01-08 00:00:00 | SHT.A-103-AN ADDITIONAL STALL IN THE |
| | WOMEN'S RESTROOM #207 IS REQD.TO COMPLY |
| | W/FACBC SEC.4.22.4. |
| | |
| | SHT.A-403-A FULLY ACCESSIBLE H.C.TOILET |
| | STALL IS REQD.IN THE WOMEN'S RESTROOM |
| | #119 WITH A LAVATORY LOCATED WITHIN THE |
| | STALL PER FACBC SEC.4.1.2.((6),4.17.3. |
| | |
| | SHT.A-403-AN ADDITIONAL STALL IN THE |
| | WOMEN'S RESTROOM #119 IS REQD.TO COMPLY |
| | W/FACBC SEC.4.22.4. |
| | |
| | DRINKING FOUNTAINS SHALL ALLOW FOR A |
| | FRONT APPROACH PER FACBC SEC.4.15.5(1), |
| | FIG.#27. |
| | |
| | WIDTH OF REQD.FULLY ACCESSIBLE STALL |
| | SHALL COMPLY W/FACBC SEC.4.17.3.(SEE |
| | EXCEPTION:NEW CONSTRUCTION.) |
| | |
| | SUBMIT COMPLETE ISOMETRIC DRAWING FOR |
| | THE STORM DRAINAGE SYSTEM.SHOW ALL PIPE |
| | SIZES,SQ.FOOT OF ROOF AREA DRAINED BY |
| | EACH DRAIN.COMPLY W/SPC SEC.1108.1, |
| | 1108.2,1108.3.(INCLUDE 1/2 AREA OF |
| | PARAPET WALLS PER SPC SEC.1108.3) |
| | |
| | SUBMIT CALCULATIONS FOR SECONDARY |
| | (EMERGENCY )ROOF DRAINS.INCLUDE 1/2 OF |
| | VERTICAL AREA OF PARAPET WALLS PER SPC |
| | SEC.1108.3,1109.1,1109.2,1109.3 & |
| | APPENDIX "A". |
| | |
| | A PERMIT FOR THE DOMESTIC WATER AND FIRE |
| | SERVICE IS REQD.FROM DEP.CONTACT PALM |
| | BEACH COUNTY HEALTH DEPT.A PERMIT MAY |
| | ALSO BE REQD.FROM PALM BEACH COUNTY |
| | HEALTH DEPT. |
| | |
| | PLUMBING SHEETS SHOW WATER SERVICE AS 3" |
| | AND CIVILS SHOW 2".CLARIFY. |
| | |
| | FLOOR DRAINS NOT PROPERLY VENTED.COMPLY |
| | W/SPC 901.2. |
| | |
| | SHT.P-601-VENTS FOR WATER CLOSETS SHALL |
| | COMPLY W/SPC SEC.920.2.(NOT LESS THAN |
| | 1/2 THE DIAMETER OF THE DRAIN SERVED.) |
| | |
| | SIZE TYPICAL WASTE STACKS FOR FIXTURES. |
| | COMPLY W/SPC SEC.920.2. |
| | |
| | WATER HEATER ON 2ND.FLOOR SHALL BE |
| | EQUIPPED W/PAN AND DRAIN PER COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.507.8.1. |
| | |
| | DRINKING FOUNTAINS ARE NOT SHOWN ON THE |
| | SANITARY OR WATER RISERS.COUNTYWIDE |
| | AMENDMENTS TO SPC SEC.104.2.1. |
| | |
| | WATER SUPPLY CONTROL FOR HOT WATER SHALL |
| | COMPLY W/SPC SEC.610.4.1. |
| | |
| | SUBMIT JOB SPECIFICATIONS FOR RE-REVIEW. |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |