| Plan Review Notes For Permit 00011033 |
| Permit Number |
00011033 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ACCEPTED BY REVISION SEE LATEST NOTES* | | | | | | INSUFFICIENT INFORMATION TO REVIEW | | | PROVIDE DETAILS ON OUTSIDE AIR PER | | | ASHRAE 62-89 | | | EXHAUST FANS ON SHT M-103 ARE LABELED TO | | | SERVE 1ST FLOOR WHAT SERVES SECOND FLOOR | | | PROVIDE DETAIL ON DUCT PENETRATING FROM | | | ROOF TO 1ST FLOOR | | | INDICATE ANY REQUIREMENTS FOR FIRE PROT- | | | ECTION AT ALL PENETRATIONS | | | PROVIDE DETAILS ON DUCT, SIZE, MATERIAL | | | AND LOCATION | | | PROVIDE CONDENSATE DRAIN INFORMATION | | | PROVIDE INFORMATION ON REQUIRED FAN SHUT | | | DOWN BY DUCT SMOKE DETECTORS |
|