| Plan Review Notes For Permit 00011001 |
| Permit Number |
00011001 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** PROVISO***************** | | | | | | 1)NOTE: PLEASE REVISE RISER DIAGRAM. | | | CLARIFY RISER? YOU SHOW 2P 250 GOING TO | | | 250 MLO PANEL WITH 1/0 AS CONDUCTORS. | | | AS PER 310-16,,,,1/0 IS ONLY RATED FOR | | | 150AMPS. | | | ALSO PLEASE CHECK LOAD CALCULATIONS. | | | BATH CIRCUTCAN BE FIGURED UNDER LIGHT- | | | -ING LOAD. DOES NOT NEED FIGURED SEPAR- | | | ATE. PLEASE CHECK HEATING UNDER OPTIONAL | | | METHOD IN THE NEC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL BEFORE ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|