| Plan Review Notes For Permit 00010990 |
| Permit Number |
00010990 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********DENIED*********************** | | | 1)PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 2)PROVIDE DETAIL ON FAN SHUT DOWN BY | | | DUCT SMOKE DETECTORS, AS REQUIRED BY | | | 1997 SMC 406 AND NFPA 90A | | | 3) ROOFTOP EQUIPMENT STANDS TO HAVE MIN. | | | 18" CLEARANCE FROM ROOF SURFACE TO | | | BOTTOM OF SUPPORT STRUCTURE OF STAND | | | PER LOCAL AMENDMENTS |
|