Plan Review Notes
Plan Review Notes For Permit 00010891
Permit Number 00010891
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** PROVISO ***************
  
 1)NOTE: PLEASE SUBMIT THE LOAD CALCU-
 -LATION SHOWING ALL THE APPLIANCES.
  
 2)NOTE: SUBMIT THE PANEL SCHEDULES FOR
 BOTH PANELS; HOUSE AND GARAGE.
  
 3)NOTE:SUBMIT NEW GARAGE RISER TO SHOW
 WIRE SIZES,CONDUITS, UNDER/OVER SERVICE
 ENTRANCE. SHOW GROUNDING ELECTRODE
 SYSTEM; TO INCLUDE BLDG.STEEL,GROUND ROD
 AND COLD WATER PIPE IF ANY IN GARAGE.
  
 4)NOTE: IF EXISTING PANEL IS BEING MOVED
 INSIDE THEN PLEASE INDICATE WEATHER OR
 NOT THE EXISTING WIRE ETC. IS STAYING
 THE SAME?WHAT SIZE & TYPE? ALSO PLESE
 SHOW THE EXISTIG GROUNDING SYSTEM.
  
 5)NOTE:AS REQ`D BY NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS. OVER 50%
 OF THE ELELCTRICAL WORK IS BEING DONE
 ALL ELECTRICAL MUST BE BROUGHT UP TO
 NEC AND ANY APP.LOCAL CODES.
  
 6)NOTE: PLEASE INDICATE ALL OUTLETS
 SERVIGN KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED. AS REQ`D BY ART;210-8-A-6
 OF THE NEC.
  
 PLEASE ALSO NOTE THE TYPE OF LIGHT FIX-
 -TURE AND CLEARENCES REQ`D BY 410-8
 IN THE MASTER BEDROOMS CLOSETS.
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL BEFORE
 THE FIRST ROUGH ELECTRICAL INSPECTION
 IS CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372