| Date |
Text |
| 2001-01-08 00:00:00 | PLANS ARE NOT DESIGNED TO THE 1997 SBC. |
| | NOTES ON PLAN S SPECIFY 1994EDITION. |
| | |
| | FILL OUT THE HEADING ON THE DESIGN COMPL |
| | IANCE FORM. NEEDS ADDRRESS |
| | |
| | PLANS INCLUDE MULTIPLE OPTIONS AND |
| | ELEVATIONS.SUBMIT PLANS FOR ONLY THE |
| | THE OPTIONS TO BE USED. |
| | |
| | |
| | THE TYPICAL WALL SECTION REFERS TO THE |
| | INVALID SSTD 10-93.CANNOT MIX DESIGN |
| | CRITERIAS,SSTD AND SBC. |
| | |
| | |
| | FRONT ENTRY DOORS WHICH ARE SERVING AS |
| | THE EGRESS FOR THE HOUSE ARE REQUIRED TO |
| | PROVIDE 32" CLEAR OPENING WHEN ONE DOOR |
| | LEAF IS OPENED. |
| | |
| | |
| | PLANS ARE REQIRED TO BE SPECIFIC. |
| | PROVIDE THE ADDRESS ON THE PLANS. |
| | |
| | |
| | |
| | ROOF TILE PRODUCT APPROVAL, THE PALM |
| | BEACH COUNTY CHECK LIST IS INVALID SINCE |
| | THE PROPOSED TILES HAVE METRO DADE |
| | APPROVAL. |
| | |
| | |
| | ROOF TILE, SPECIFY THE METHOD OF ATTACH- |
| | MENT.IF NAIL ON SYSTEM PROVIDE THE |
| | ATTACHMENT CALCULATIONS,SEE PAGE 10 |
| | OF THE PRODUCT APPROVAL. |
| | |
| | |
| | |
| | PROVIDE PRODUCT APPROVAL FOR THE |
| | OVERHEAD GARAGE DOOR. |
| | |
| | |
| | NORANDEX PRODUCT APPROVAL IS REQUIRED TO |
| | HAVE THE DESIGNER OF RECORD RAISED SEAL. |
| | |
| | |
| | THE HEAT GAIN AND LOSS SPECIFYS THE 3650 |
| | MODEL THIS IS THE 3576 MODEL, CLARIFY. |
| | |
| | |
| | ENERGY FORM 600A,COMPLETE HEADING AND |
| | NEEDS OWNER AGENT SIGNATURE. |
| | |
| | |
| | THE WIND PRESURES FOR THE OVERHEAD |
| | GARAGE DOOR DOES AS STATED IN SCHEDULE |
| | ARE +28 & -30.I CALCULATE THE PRES- |
| | URE AS FOLLOWS 28.3 (FROM 1606.2A) TIMES |
| | 1.2 (1606.2C) = -33.96 AND 28.3 TIMES |
| | 1.1= +31.13.CLARIFY |
| | |
| | |
| | STAIR THREAD AND RISER DO NOT MEET SECT. |
| | 1007.3 (2RISER + 1 THREAD). ALSO THREAD |
| | NEEDS TO BE A MIN OF 9" EXCLUSIVE OF |
| | NOSING. |
| | |
| | PROVIDE DETAIL FOR CONSTRUCTING THE |
| | STAIR GUARDRAIL IN ACCORDANCE WITH SECT. |
| | 1015.5 SBC 1997. |
| | |
| | |
| | THE PRODUCT APPROVAL FOR THE HURRICANE |
| | SHUTTERS NEEDS TO INCLUDE A PLAN LAYOUT |
| | WITH THE OPENINGS IDENTIFIED. |
| | |
| | NOT ALL ABOVE ITEMS COMPLETE 4/3/00. |
| | CHECK LIST WRITTEN AND ATTACHED TO PLANS |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | . |