2001-03-06 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT`S
 ON PLANS AND CORRELATE WIH PANEL SCHED-
 -ULR.
  
 2)NOTE: PLEASE NOTE THAT ELECTRICAL
 RISER DIAGRAM AND PANELS DO NOT MATCH,
 ONE SHOWS 200A AND THE OTHER 225A WITH
 WIRE RATED FOR 200A??
  
 3)NOTE: PLEASE LABEL ALL BRANCH CIRCUIT
 #`S ON PLANS THAT CORRELATE WITH SUBMITT
 ED PANEL SCHEDULES
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372