| Date |
Text |
| 2001-01-08 00:00:00 | ************** PROVISO **************** | | | | | | 1)NOTE:AS PER OUR CONVERSATION PLEASE | | | CHECK FAULT CURRENT CALCULATIONS FOR | | | AIC RATING. FPL CAN GIVE FALUT CURRENT | | | AVAILABILITY. | | | | | | 2)NOTE:PLEASE SHOW GROUNDING ELECTRODE | | | CONDUCTOR GOING TO BLDG.STEEL ALSO AS S | | | REQ`D BY 250-81 FO THE NEC. | | | | | | 3)NOTE: BATH(S) CIRCUT DOES NOT NEED TO | | | BE INCLUDED IN LOAD CALCULATION BUT | | | NEEDS TO BE ON PANEL SCHEDULE. | | | | | | 4)NOTE: RISER DIAGRAM SHOWS FEEDTO | | | PANEL GOING OVERHEAD. IF THIS IS THE | | | CASE THERE CANNOT BE OVER 8`OF CONDUCTOR | | | INSIDE THE STRUCTURE AS PER ART;230-70A | | | OF THE NEC. IF IT IS GOING TO BE IN- | | | -STALLED IN SLAB THEN PLEASE SHOW. | | | | | | PLESE HAVE ALL THE ABOVE INFORMATION | | | SUBMITTED FOR REVIEW AND APPROVAL BEFORE | | | FIRST ROUGH ELECTRICAL INSPECTION IS | | | CALLED IN. IF THERE ARE ANY QUESTIONS; | | | CALL; 561-659-8096 EXT 8372 |
|