Plan Review Notes
Plan Review Notes For Permit 00010492
Permit Number 00010492
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT SQ.FOOTAGE OF STRUCTURE AND
 OCCUPANT LOAD TO ENSURE COMPLIANCEW/
 TABLE 407 OF SPC.
  
 BREAKROOM SINK SHALL BE HANDICAP ACCESS-
 IBLE PER FACBC SEC.4.24.1-4.24.7.
  
 WALLS AND FLOORS IN TOILET ROOMS SHALL
 BE NON-ABSORBENT TO A HEIGHT OF 4" PER
 SBC SEC.1204.2.
  
 HEIGHT OF H.C.WATER CLOSET SHALL COMPLY
 W/FACBC SEC.4.16.3.(17"-19").
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER FACBC SEC.501.7.SUPPLY PERMANENT
 LADDER OR RELOCATE EWH TO FLOOR.
  
 SHT.PO.1-"M" COPPER NOT PERMITTED U/G
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 611.3.
  
 NO MORE THAN 2 FIXTURES SHALL BE
 CONNECTED TO 1/2" C.W.LINE PER COUNTY-
 WIDE AMENDMENTS TO SPC SEC.607.7.
  
 WATER RISER SHOWS 1/2" LINE SUPPLYING
 3/4" TO URINALS.SPC TABLE 607.
  
 CONNECTION OF CONDENSATE DRAINS TO STORM
 DRAINAGE SYSTEM SHALL BE BY INDIRECT
 CONNECTIONS PER COUNTYWIDE AMENDMENTS
 TO SPC SEC.804.3.