| Plan Review Notes For Permit 00010492 |
| Permit Number |
00010492 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT SQ.FOOTAGE OF STRUCTURE AND | | | OCCUPANT LOAD TO ENSURE COMPLIANCEW/ | | | TABLE 407 OF SPC. | | | | | | BREAKROOM SINK SHALL BE HANDICAP ACCESS- | | | IBLE PER FACBC SEC.4.24.1-4.24.7. | | | | | | WALLS AND FLOORS IN TOILET ROOMS SHALL | | | BE NON-ABSORBENT TO A HEIGHT OF 4" PER | | | SBC SEC.1204.2. | | | | | | HEIGHT OF H.C.WATER CLOSET SHALL COMPLY | | | W/FACBC SEC.4.16.3.(17"-19"). | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER FACBC SEC.501.7.SUPPLY PERMANENT | | | LADDER OR RELOCATE EWH TO FLOOR. | | | | | | SHT.PO.1-"M" COPPER NOT PERMITTED U/G | | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 611.3. | | | | | | NO MORE THAN 2 FIXTURES SHALL BE | | | CONNECTED TO 1/2" C.W.LINE PER COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.607.7. | | | | | | WATER RISER SHOWS 1/2" LINE SUPPLYING | | | 3/4" TO URINALS.SPC TABLE 607. | | | | | | CONNECTION OF CONDENSATE DRAINS TO STORM | | | DRAINAGE SYSTEM SHALL BE BY INDIRECT | | | CONNECTIONS PER COUNTYWIDE AMENDMENTS | | | TO SPC SEC.804.3. |
|