2001-01-08 00:00:00************** UNSAT ***************
  
 1)NOTE:PLEASE NOTE THAT YOU SHOW THE
 EXISTING PANEL BEING RELOCATED TO NEW
 AREA.AS REQ`D BY ART;230-70-A FO THE
 NEC. THERE MUST BEA MAIN DISC.IF THERE
 IS MORE THAN 8`FT OF UNPROTECTED
 CONDUCTORS INSIDE THE STRUCTURE.
 MIAN WILL BE REQ`D AND NEEDS TO BE SHOWN
 ON NEW RISER DIAGRAM. EXISTING PANEL
 SHOWS MLO ANYWAY??? WHERE IS THE EXIST-
 -ING MAIN??
  
 2)NOTE:PERTAINING TO THE #6 GROUND SHOWN
 FROM EXISTINGMETER TO PANEL.THERE
 SHOULDN`T BE ONE. ONLY AFTER FIRST MEANS
 OF DISC.
  
 3)NOTE: PLEASE INDICATE ON PANEL SCHED.
 THE REQ`D BATH(S) CIRCUT(S) AS PER ART;
 210-52D/ 215-5 OF THE NEC.
  
 4)NOTE:ALL OUTLETS SERVING KITCHEN
 COUNTERSPACE ARE TO BE GFI/GFI PROTECTED
 AS PER 210-8-A-6.
  
 5)NOTE:AS REQ`D BY 210-8 OF THE NEC. THE
 RECEPT. BEING ADDED TO GARAGE IS TO BE
 GFI/GFI PROTECTED.
  
 6)NOTE:AS PER NFPA-72 SMOKE DETECTORS
 WILL BE REQ`D INSIDE AND OUTSIDE THE
 SLEEPING ROOMS AND ANY ROOMS WITH CLOSET
 SPACE HAVING THE ABILITY OF BEING CON-
 VERTED TO SLEEPING ROOMS.
  
 7)NOTE:PLEASE REFIGURE LOAD CALCULATIONS
 THE HEAT SHOWN IS NOT CLEAR. YOU SHOW
 10KW ON PANEL SCHEDULE BUT CALC. DOES
 NOT CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372