| 2001-01-08 00:00:00 | ************** UNSAT *************** |
| | |
| | 1)NOTE:PLEASE NOTE THAT YOU SHOW THE |
| | EXISTING PANEL BEING RELOCATED TO NEW |
| | AREA.AS REQ`D BY ART;230-70-A FO THE |
| | NEC. THERE MUST BEA MAIN DISC.IF THERE |
| | IS MORE THAN 8`FT OF UNPROTECTED |
| | CONDUCTORS INSIDE THE STRUCTURE. |
| | MIAN WILL BE REQ`D AND NEEDS TO BE SHOWN |
| | ON NEW RISER DIAGRAM. EXISTING PANEL |
| | SHOWS MLO ANYWAY??? WHERE IS THE EXIST- |
| | -ING MAIN?? |
| | |
| | 2)NOTE:PERTAINING TO THE #6 GROUND SHOWN |
| | FROM EXISTINGMETER TO PANEL.THERE |
| | SHOULDN`T BE ONE. ONLY AFTER FIRST MEANS |
| | OF DISC. |
| | |
| | 3)NOTE: PLEASE INDICATE ON PANEL SCHED. |
| | THE REQ`D BATH(S) CIRCUT(S) AS PER ART; |
| | 210-52D/ 215-5 OF THE NEC. |
| | |
| | 4)NOTE:ALL OUTLETS SERVING KITCHEN |
| | COUNTERSPACE ARE TO BE GFI/GFI PROTECTED |
| | AS PER 210-8-A-6. |
| | |
| | 5)NOTE:AS REQ`D BY 210-8 OF THE NEC. THE |
| | RECEPT. BEING ADDED TO GARAGE IS TO BE |
| | GFI/GFI PROTECTED. |
| | |
| | 6)NOTE:AS PER NFPA-72 SMOKE DETECTORS |
| | WILL BE REQ`D INSIDE AND OUTSIDE THE |
| | SLEEPING ROOMS AND ANY ROOMS WITH CLOSET |
| | SPACE HAVING THE ABILITY OF BEING CON- |
| | VERTED TO SLEEPING ROOMS. |
| | |
| | 7)NOTE:PLEASE REFIGURE LOAD CALCULATIONS |
| | THE HEAT SHOWN IS NOT CLEAR. YOU SHOW |
| | 10KW ON PANEL SCHEDULE BUT CALC. DOES |
| | NOT CORRELATE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND APPROVAL. IF THERE ARE ANY |
| | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |