Plan Review Notes
Plan Review Notes For Permit 00010411
Permit Number 00010411
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT SQ.FOOTAGE OF TENANT SPACE FOR
 OCCUPANT LOAD TO ENSURE COMPLIANCE W/SPC
 TABLE 407 FOR MINIMUM FIXTURE REQS.
  
 LOUNGE SINK SHALL COMPLY W/FACBC SECS.
 4.24.1-4.24.7.
  
 A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407 AND SHALL COMPLY W/FACBC SEC.
 4.1.3(10)(A),4.15.1-4.15.5.
  
 WIDTH OF HANDICAP TOILET STALLS SHALL
 COMPLY W/FACBC SEC.4.17.3(EXCEPTION:NEW
 CONSTRUCTION.)
  
 MAX.HEIGHT OF URINAL SHALL BE 17" PER
 FACBC SEC.4.18.1-4.18.4.
  
 ALL TOILET ROOMS IN HEALTH CARE
 FACILITIES SHALL HAVE FLOOR DRAINS PER
 SPC 409.4.1.1(EXCEPTION)
  
 FLOORS AND WALLS IN TOILET ROOMS SHALL
 BE IMPERVIOUS TO A HEIGHT OF 4' PER SBC
 SEC.1204.2.
  
 SHOWER IN MASSAGE ROOM SHALL BE HANDICAP
 ACCESSIBLE PER FACBC SEC.4.1.3.(11),
 4.23.8.
  
 SUBMIT A WATER RISER DIAGRAM FOR REVIEW
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1,610.4.2.
  
 SHOWER VALVES SHALL COMPLY W/SPC SEC.
 613.1/TABLE 613.