| Plan Review Notes For Permit 00010411 |
| Permit Number |
00010411 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SUBMIT SQ.FOOTAGE OF TENANT SPACE FOR | | | OCCUPANT LOAD TO ENSURE COMPLIANCE W/SPC | | | TABLE 407 FOR MINIMUM FIXTURE REQS. | | | | | | LOUNGE SINK SHALL COMPLY W/FACBC SECS. | | | 4.24.1-4.24.7. | | | | | | A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407 AND SHALL COMPLY W/FACBC SEC. | | | 4.1.3(10)(A),4.15.1-4.15.5. | | | | | | WIDTH OF HANDICAP TOILET STALLS SHALL | | | COMPLY W/FACBC SEC.4.17.3(EXCEPTION:NEW | | | CONSTRUCTION.) | | | | | | MAX.HEIGHT OF URINAL SHALL BE 17" PER | | | FACBC SEC.4.18.1-4.18.4. | | | | | | ALL TOILET ROOMS IN HEALTH CARE | | | FACILITIES SHALL HAVE FLOOR DRAINS PER | | | SPC 409.4.1.1(EXCEPTION) | | | | | | FLOORS AND WALLS IN TOILET ROOMS SHALL | | | BE IMPERVIOUS TO A HEIGHT OF 4' PER SBC | | | SEC.1204.2. | | | | | | SHOWER IN MASSAGE ROOM SHALL BE HANDICAP | | | ACCESSIBLE PER FACBC SEC.4.1.3.(11), | | | 4.23.8. | | | | | | SUBMIT A WATER RISER DIAGRAM FOR REVIEW | | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | | SEC.610.4.1,610.4.2. | | | | | | SHOWER VALVES SHALL COMPLY W/SPC SEC. | | | 613.1/TABLE 613. |
|