| Plan Review Notes For Permit 00010370 |
| Permit Number |
00010370 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW# 102 | | | DENIED | | | (1) SHT-2 BOTTLED WATER DISPENSER NOT | | | PERMITED IN LEIU OF DRINKING FOUNTAIN, | | | ALSO TO COMPLY WITH ADA ACCESSIBLE | | | FACBC 4.1.3 (10)(A), SPC TAB 407. | | | (2) FLOOR DRAINS REQUIRED WITH TRAP | | | PRIMERS IN REST RMS SEC 409.4 EXCEPTION. | | | (3)INFORMATION ON WASTE FROM PROCESSOR | | | FOR PH LEVEL. | | | (4) ALL EQUIPMENT CONNECTED TO THE WATER | | | SULLLY TO BE PROTECTED WITH A APPROVED | | | BACK FLOW PREVENTER. | | | (5) BREAK ROOM SINK TO BE ADA ACCESSIBLE | | | 34" HIGH COUNTER TOP. 4.24 TO4.24.7 | | | FACBCEND OF COMMENTS |
|