Plan Review Notes
Plan Review Notes For Permit 00010370
Permit Number 00010370
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 1) TIE NEW A/C UNIT TO BUILDING FIRE
 ALARM WITH DUCT SMOKE DETECTOR
 2) MEDICAL GAS REQUIRES MECHANICAL PER-
 MIT. PROVIDE DETAILS AND SPECS WITH PLAN
 FOR REVIEW AT TIME OF MECHANICAL PERMIT
 APPLICATION, INCLUDE EQUIPMENT LOCATION
 AND EXHAUST TERMINATION FOR VACUUM AND
 SOURCE OF AIR FOR COMPRESSED AIR UNIT.
 INSTALLATION TO COMPLY WITH NFPA 99C