| Plan Review Notes For Permit 00010279 |
| Permit Number |
00010279 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | | EQUIPMENT MAINS. MAINS NEED TO BE RATED | | | FOR THE AVAILABLE FAULT CURRENT.AS REQ`D | | | BY ARTS;110-9/110-10 AND 215-5 OF THE | | | NEC. | | | | | | 2)NOTE:AS REQ`D BY NFPA-72 2-2.1.1.1 | | | SMOKE DETECTORS ARE REQ`D INSDIE AND | | | OUTSIDE ALL SLEEPING ROOMS. | | | | | | 3)NOTE:PLEASE HAVE THE DEDICATED BATH(S) | | | CIRCUT(S) LISTE ON PANEL SCHEDULE. MUST | | | BE 20 AMP AND #12 AWG. THIS IS REQ`D BY | | | ART;210-52D | | | | | | 4)NOTE: NEED TO HAVE OUTLET MARKED ON | | | WALL BY FRONT DOOR PER 210-52 OR 210-52H | | | | | | PLEASE NOTE A/C AND METER LOCATION AND | | | CLEARANCES REQ`D BY 110-16 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND APPROVAL.IF THERE ARE ANY | | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|