| 2001-01-08 00:00:00 | ************UNSAT******************* |
| | |
| | 1)NOTE:NEED TO SUBMIT SERVICE SIZE!! |
| | TO INCLUDE SIZE OF EXISTING METERCAN. |
| | SUBMIT COMPLETE AND TOTAL LOAD |
| | CALCULATIONS ON 200A MAIN PANEL. |
| | IF EXISTING 100 PANEL SHOWN ISCOMING FRO |
| | METER WITH NO MAIN THEN MAIN DISC. MUST |
| | BE INSTALLED. MIANS MUST BE GROUPED!!! |
| | SHOW HOW NEW PANEL 'C' IS BEING FED. IS |
| | IT COMING FROM EXISITING 200A PANEL? |
| | IS THERE GOING TO BE A MAIN BRKR IN |
| | PANEL 'A' FOR PANEL 'C'???? |
| | GIVE COMPLETE DETAILED PANEL SCHEDULES |
| | FOR ALL PANELS. |
| | ALL MAINS MUST BE GROUPED PER 230-72!!! |
| | SHOW ALL EXISTING WIRE SIZES FOR SERVICE |
| | TO INCLUDE # OF CONDUCTORS IN EACH PIPE. |
| | ALL THE ABOVE FALLS UNDER THE FOLLOWING |
| | PROVIDE AIC RATINGS OF NEW EQUIPMENT |
| | BEING INSTALLED. AIC RATING IS FIGURED |
| | FROM FAULT CURRENT CALCULATIONS. |
| | |
| | ALL THE ABOVE ITEMS ARE FROM THE FOLLOW- |
| | -ING ARTS IN THE NEC,,,310-16/215-5/230- |
| | 65/220-3-D-1/230-72 |
| | |
| | 2)NOTE:AS PER NFPA-72 2-2.1.1.1 SMOKE |
| | DETECTORS ARE REQ`D INSIDE AND OUTSIDE |
| | ALL SLEEPING ROOMS IN ANY NEW CONST. |
| | BY CODE MORETHAN 50% OF THE ELECTRIC |
| | IS BEING DONE,,,SMOKE DETECTORS ARE |
| | GOING TO BE REQ`D IN EXISTING SLEEPING |
| | ROOMS. |
| | |
| | 3)NOTE: PLEASE LIST DEDICATED BATH(S) |
| | CIRCUT(S) WHICH ARE REQ`D BY 210-52D. |
| | THEY ARE TO BE 20AMP AND #12 AWG. |
| | SHOW FOR NEW BATH IN ADDITION. |
| | |
| | )NOTE:SEEING THAT MORETHAN 50% OF ELEC. |
| | IS BEING DONE. THEN FIELD INSPECTOR |
| | MAY REQ OTHER ELECTRICAL ITEMS TO BE |
| | BROUGHT UP TO CODE. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW AND APPROVAL!!!!ALL THE ABOVE |
| | ITEMS NEED TO BE ADDRESED.IF THERE ARE |
| | ANY QUESTIONS THEN PLEASE CALL ME AT |
| | THE FOLLOWING # 659-8096 EXT.8372 |