Plan Review Notes
Plan Review Notes For Permit 00010201
Permit Number 00010201
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************UNSAT*******************
  
 1)NOTE:NEED TO SUBMIT SERVICE SIZE!!
 TO INCLUDE SIZE OF EXISTING METERCAN.
 SUBMIT COMPLETE AND TOTAL LOAD
 CALCULATIONS ON 200A MAIN PANEL.
 IF EXISTING 100 PANEL SHOWN ISCOMING FRO
 METER WITH NO MAIN THEN MAIN DISC. MUST
 BE INSTALLED. MIANS MUST BE GROUPED!!!
 SHOW HOW NEW PANEL 'C' IS BEING FED. IS
 IT COMING FROM EXISITING 200A PANEL?
 IS THERE GOING TO BE A MAIN BRKR IN
 PANEL 'A' FOR PANEL 'C'????
 GIVE COMPLETE DETAILED PANEL SCHEDULES
 FOR ALL PANELS.
 ALL MAINS MUST BE GROUPED PER 230-72!!!
 SHOW ALL EXISTING WIRE SIZES FOR SERVICE
 TO INCLUDE # OF CONDUCTORS IN EACH PIPE.
 ALL THE ABOVE FALLS UNDER THE FOLLOWING
 PROVIDE AIC RATINGS OF NEW EQUIPMENT
 BEING INSTALLED. AIC RATING IS FIGURED
 FROM FAULT CURRENT CALCULATIONS.
  
 ALL THE ABOVE ITEMS ARE FROM THE FOLLOW-
 -ING ARTS IN THE NEC,,,310-16/215-5/230-
 65/220-3-D-1/230-72
  
 2)NOTE:AS PER NFPA-72 2-2.1.1.1 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS IN ANY NEW CONST.
 BY CODE MORETHAN 50% OF THE ELECTRIC
 IS BEING DONE,,,SMOKE DETECTORS ARE
 GOING TO BE REQ`D IN EXISTING SLEEPING
 ROOMS.
  
 3)NOTE: PLEASE LIST DEDICATED BATH(S)
 CIRCUT(S) WHICH ARE REQ`D BY 210-52D.
 THEY ARE TO BE 20AMP AND #12 AWG.
 SHOW FOR NEW BATH IN ADDITION.
  
 )NOTE:SEEING THAT MORETHAN 50% OF ELEC.
 IS BEING DONE. THEN FIELD INSPECTOR
 MAY REQ OTHER ELECTRICAL ITEMS TO BE
 BROUGHT UP TO CODE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND APPROVAL!!!!ALL THE ABOVE
 ITEMS NEED TO BE ADDRESED.IF THERE ARE
 ANY QUESTIONS THEN PLEASE CALL ME AT
 THE FOLLOWING # 659-8096 EXT.8372